Technical Guide
718445-YTG-A-0811
30 Johnson Controls Unitary Products
Electrical Data
DNQ024-060 Gas Heat
Size
(Tons)
DNQ
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
Max
Fuse
2
/
Breaker
3
Size
(Amps)
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
RLA LRA MCC FLA FLA
024
(2.0)
208/230-1-60 8.3 43 13 1.4 4.3 16.1 20
030
(2.5)
208/230-1-60 14.1 73 22 1.4 6.8 25.8 35
208/230-3-60 8.9 58 14 1.4 6.8 19.3 25
460-3-60 4.2 28 7 0.8 3.4 9.5 15
036
(3.0)
208/230-1-60 14.1 77 22 1.4 6.8 25.8 35
208/230-3-60 9.0 71 14 1.4 6.8 19.5 25
460-3-60 5.6 38 9 0.8 3.4 11.2 15
042
(3.5)
208/230-1-60 21.8 105 34 1.7 9.1 38.1 50
208/230-3-60 14.1 95 22 1.7 9.1 28.4 35
460-3-60 6.4 45 10 0.9 4.6 13.5 15
048
(4.0)
208/230-1-60 20.5 115 32 1.7 9.1 36.4 45
208/230-3-60 16.0 120 25 1.7 9.1 30.8 40
460-3-60 7.7 50 12 0.9 4.6 15.1 20
060
(5.0)
208/230-1-60 25.0 134 39 2.8 9.1 43.2 60
208/230-3-60 15.9 110 25 2.8 9.1 31.8 40
460-3-60 7.7 52 12 1.4 4.6 15.6 20