TABLE 37: 6-1/2 TON STANDARD MOTOR SIDE SHOT BLOWER PERFORMANCE
*
ESP
TURNS OPEN
**
012345
CFM
W
††
BHP CFM
W
††
BHP CFM
W
††
BHP CFM
W
††
BHP CFM
W
BHP CFM
W
BHP
0.4
- - - - - - 3367 1216 1.30 3133 1067 1.14 2954 944 1.01 2701 819 0.88
0.6
- - - 3208 1239 1.33 2913 1068 1.15 2466 913 0.98 2350 789 0.85 1750 621 0.67
0.8
- - - 2651 1058 1.13 2317 894 0.96 1656 700 0.75 - - - - - -
1.0
2186 998 1.07 1774 830 0.89 - - - - - - - - - - - -
*.
Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.
.
Blower performance includes two-inch throwaway filters.
.
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been
deducted from the total static pressure of the blower.
**.
Turns Open refers to the setting of the variable pitch motor sheave, where 0 Turns Open is fully closed.
††.
W = Watts
TABLE 38: 6-1/2 TON OPTIONAL MOTOR SIDE SHOT BLOWER PERFORMANCE
*
ESP
TURNS OPEN
**
012345
CFM
W
††
BHP CFM
W
††
BHP CFM
W
††
BHP CFM
W
††
BHP CFM
W
††
BHP CFM
W
††
BHP
0.6
- - - - - - - - - - - - - - - 3597 1598 1.71
0.8
- - - - - - - - - - - - 3503 1689 1.81 3172 1430 1.53
1.0
- - - - - - 3406 1778 1.91 3032 1497 1.61 2248 1143 1.23
1.2
- - - - - - 3327 1866 2.00 2926 1578 1.69 2160 1217 1.31 - - -
1.4
- - - 3270 1971 2.11 2537 1544 1.66 2043 1296 1.39 - - - - - -
1.6
3196 2077 2.23 2460 1651 1.77 1858 1318 1.41 - - - - - - - - -
1.8
2426 1768 1.90 - - - - - - - - - - - - - - -
*.
Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.
.
Blower performance includes two-inch throwaway filters.
.
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been
deducted from the total static pressure of the blower.
**.
Turns Open refers to the setting of the variable pitch motor sheave, where 0 Turns Open is fully closed.
††.
W = Watts