Specifications

035-17377-000 (0201) REV A
10 Unitary Products Group
CLEARANCES
All units require particular clearances for proper operation
and service. Installer must make provisions for adequate
combustion and ventilation air in accordance with section 5.3
of Air for Combustion and Ventilation of the National Fuel Gas
Code, ANSI Z223.1 Latest Edition, or Sections 7.2, 7.3, or
7.4 of Installation Codes, CSA-B149 - Latest Edition, and/or
applicable provisions of the local building codes. Refer to
Table 10 for clearances required for combustible construc-
tion, servicing, and proper unit operation.
TABLE 8: 4 POINT LOAD WEIGHT
Model
Location (lbs.)
*
ABCD
DM078
228 195 285 333
DM090
230 197 287 336
DM102
238 203 296 347
DM120
245 209 305 357
DM150
262 224 327 382
DH078
241 206 300 352
DH090
242 207 301 353
DH102
257 220 321 375
DH120
265 226 330 386
DH150
263 224 327 383
*.
Weights include largest gas heat option.
TABLE 9: 6 POINT LOAD WEIGHT
Model
Location (lbs.)
*
*.
Weights include largest gas heat option.
ABCDEF
DM078
156 140 127 185 205 228
DM090
158 142 128 187 207 230
DM102
163 146 132 192 213 237
DM120
168 151 136 198 219 244
DM150
180 161 145 212 235 262
DH078
165 148 134 195 216 241
DH090
166 149 134 196 217 242
DH102
176 158 143 208 231 257
DH120
181 163 147 214 237 264
DH150
180 161 146 213 235 262
FIGURE 7 : UNIT CENTER OF GRAVITY
FIGURE 6 : UNIT 6 POINT LOAD
Do not permit overhanging structures or shrubs to
obstruct condenser air discharge outlet, combus-
tion air inlet or vent outlets.