Specifications

392856-YTG-C-0109
Johnson Controls Unitary Products 9
TABLE 2: CAPACITY RATINGS - (ARI 210/240)
1
1. 80/67°F Indoor and 95°F outdoor.
MODEL MBH
EER
2
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).
DM072
72.0 9.0
TABLE 3: GAS HEAT RATINGS
1
1. All units are single-stage heating.
MODEL
MBH
INPUT
MBH
OUTPUT
AFUE
(%)
TEMP
RISE ºF
DM072N08
100 80 80.5 25 - 55
DM072N10
125 100 80.3 30 - 75
TABLE 4: 2 STAGE GAS HEAT RATINGS
MODEL
1,
2
1. Models are 3Ø only.
2. All 2 Stage Gas Heat, 60% Capacity 1
ST
Stage, 40% Capacity 2
ND
Stage.
MBH INPUT MBH OUTPUT STEADY STATE EFFICIENCY RISE
MINIMUM HEATING
AIRFLOW (CFM)
1
ST
STAGE 2
ND
STAGE 1
ST
STAGE 2
ND
STAGE 1
ST
STAGE 2
ND
STAGE MIN. MAX.
DM072D06
45 75 35.8 60.8 79.4 81.1 15 45 1230
DM072D10