036-21687-002-A-1105 ® DESCRIPTION YORK Sunline Magnum™ units are convertible single package air conditioners with a common cabinet and a common roof curb for the 3, 4 and 5 ton sizes. The units were designed for light commercial and commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame.
036-21687-002-A-1105 TABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . 12 FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . 13 GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 43 LIST OF FIGURES 11 DJ048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE) . . . . . . . . . .
036-21687-002-A-1105 PRODUCT NOMENCLATURE 7RQ 6XQOLQH 0DJQXP 0RGHO 1XPEHU 1RPHQFODWXUH ' - 1 1 $ $$ 3URGXFW *HQHUDWLRQ 3URGXFW &DWHJRU\ )LUVW *HQHUDWLRQ ' $LU &RQG 6LQJOH 3NJ 5 9ROWDJH 3URGXFW ,GHQWLILHU - 8OWUD (IILFLHQF\ %HOW 'ULYH 2QO\ 1RPLQDO &RROLQJ &DSDFLW\ 0%+ ,QVWDOODWLRQ 2SWLRQV 7RQ 7RQ 7RQ $ 1R 2SWLRQV ,QVWDOOHG $GGLWLRQDO 2SWLRQV 6HH 1H[W 3DJH % 2SWLRQ & 2SWL
036-21687-002-A-1105 PRODUCT NOMENCLATURE - Continued 3-5T Sunline Model Number Nomenclature Standard Cabinet AA AB AC AD AE AF AG AH AJ AK AL AM AN AS CA CB CC CD CE CF CG CH CJ CK CL CM CN CP CQ CR CS CT CU CV CW CX JA JB JC JD JE JF JG JH JJ JK JL JM JN JP JQ 4 None Phase Monitor Coil Guard Dirty Filter Switch Phase Monitor & Coil Guard Phase Monitor & Dirty Filter Switch Coil Guard & Dirty Filter Switch Phase Monitor, Coil Guard, & Dirty Filter Switch SS Drain Pan SS Drain Pan & Phase Monitor SS Dra
036-21687-002-A-1105 Standard Cabinet JR JS JT JU JV JW JX HA HB HC HD HE HF HG HH HJ HK HL HM HN HP HQ HR HS HT HU HV HW HX NA NB NC ND NE NF NG NH NJ NK NL NM NN NP NQ NR NS NT NU NV NW NX TA TB TC Johnson UNT Controller, DFS, APS, Technicoat Evap.
036-21687-002-A-1105 Standard Cabinet TD TE TF TG TH TJ TK TL TM TN TP TQ TR TS TT TU TV TW TX TY TZ T1 T3 T4 T6 T7 T9 LA LB LC LD LE LF LG LH LJ LK LL LM LN LP LQ LR LS LT LU LV LW LX WA WB WC WD WE 6 Technicoat Condenser Coil & Dirty Filter Switch Technicoat Condenser Coil, Phase Monitor, & Coil Guard Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch Tec
036-21687-002-A-1105 Standard Cabinet WF WG WH WJ WK WL WM WN WP WQ WR WS WT WU WV WW WX Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil Intelli-Comfort w/Mod Link Controller, Technicoat Evap.
036-21687-002-A-1105 Hinged Filter Door & Toolless Access Cabinet DX EA EB EC ED EE EF EG EH EJ EK EL EM EN EP EQ ER ES ET EU EV EW EX GA GB GC GD GE GF GG GH GJ GK GL GM GN GP GQ GR GS GT GU GV GW GX PA PB 8 CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels Johnson UNT Controller, DFS, APS & Phase M
036-21687-002-A-1105 Hinged Filter Door & Toolless Access Cabinet PC PD PE PF PG PH PJ PK PL PM PN PP PQ PR Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels Novar ETC-3 Controller, DFS, APS, Technicoat Cond.
036-21687-002-A-1105 Hinged Filter Door & Toolless Access Cabinet QD QE QF QG QH QJ QK QL QM QN QP QQ QR QS QT QU QV QW QX Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels Simplicity Intelli-Comfort Controller, Technicoat Cond.
036-21687-002-A-1105 FEATURES gas valve, if applicable, and the temperature limit switch on gas heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips. All models are available with a wide variety of factorymounted options such as stainless steel heat exchangers, electric heaters, phase monitor, convenience outlet, dirty filter switch, disconnect switch, smoke detectors, and coil guard to make them suitable for almost every application.
036-21687-002-A-1105 FIGURE 1 - UNIT CUTAWAY FACTORY-INSTALLED OPTIONS • SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers. The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
036-21687-002-A-1105 using CO2 sensors. It uses an inside CO2 sensor to perform Demand Ventilation. It can also use an Outside CO2 sensor to perform Differential Demand Ventilation. It uses a Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. The patented economizer-loading algorithm will protect the equipment when harsh operating conditions exist.
036-21687-002-A-1105 • ROOF CURBS - Eight and fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly. • • • Roof curbs are designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.
036-21687-002-A-1105 TABLE 4: DJ036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP Octave Center Freq. 63 125 250 500 1000 2000 4000 8000 630 0.2 1116 0.41 Cooling ID Blower Operation2 Only (dB) (dB) 80 82 76 77 56 59 50 50 40 43 41 42 41 41 45 45 DJ036 / 3 Ton / Belt Drive Horizontal Ducted Inlet 631 879 885 0.3 0.2 0.7 928 1979 1020 0.37 0.76 0.
036-21687-002-A-1105 TABLE 6: DJ036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP Octave Center Freq. 63 125 250 500 1000 2000 4000 8000 632 0.2 1069 0.36 Cooling ID Blower Operation2 Only (dB) (dB) 78 82 70 75 55 60 47 50 40 43 37 40 36 37 44 44 DJ036 / 3 Ton / Belt Drive Vertical Ducted Inlet 632 881 883 0.3 0.2 0.7 870 1903 917 0.33 0.71 0.
036-21687-002-A-1105 TABLE 8: DJ048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP Octave Center Freq. 63 125 250 500 1000 2000 4000 8000 766 0.2 1484 0.67 Cooling ID Blower Operation2 Only (dB) (dB) 74 97 70 86 53 58 49 55 42 42 40 44 38 44 42 43 DJ048 / 4 Ton / Belt Drive Horizontal Ducted Inlet 769 1077 1087 0.5 0.4 1.0 993 2270 1406 0.54 1.24 0.
036-21687-002-A-1105 TABLE 10: DJ048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP Octave Center Freq. 63 125 250 500 1000 2000 4000 8000 791 0.2 1408 0.54 Cooling ID Blower Operation2 Only (dB) (dB) 76 95 68 84 54 57 48 53 43 44 40 43 38 43 43 43 DJ048 / 4 Ton / Belt Drive Vertical Ducted Inlet 794 1084 1095 0.5 0.2 1.0 1000 2336 1275 0.42 1.12 0.
036-21687-002-A-1105 TABLE 12: DJ060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) 81,7 '(6&5,37,21 02'(/ &21),*85$7,21 ,QGRRU %ORZHU 6SHHG 530 %ORZHU 6WDWLF 3UHVVXUH ,:* $LUIORZ &)0 %ORZHU 0RWRU %+3 2FWDYH &HQWHU )UHT &RROLQJ ,' %ORZHU 2SHUDWLRQ 2QO\ G% G% '- 7RQ %HOW 'ULYH +RUL]RQWDO 'XFWHG ,QOHW &RROLQJ &RROLQJ &RROLQJ ,' %
036-21687-002-A-1105 TABLE 14: DJ060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) 81,7 '(6&5,37,21 02'(/ &21),*85$7,21 ,QGRRU %ORZHU 6SHHG 530 %ORZHU 6WDWLF 3UHVVXUH ,:* $LUIORZ &)0 %ORZHU 0RWRU %+3 2FWDYH &HQWHU )UHT &RROLQJ ,' %ORZHU 2SHUDWLRQ 2QO\ G% G% '- 7RQ %HOW 'ULYH 9HUWLFDO 'XFWHG ,QOHW &RROLQJ &RROLQJ &RROLQJ ,' %ORZH
036-21687-002-A-1105 TABLE 16: DJ036 COOLING CAPACITIES (3 TON) Temperature of Air on Condenser Coil Air on Evaporator Coil CFM 900 1050 1200 1350 1500 900 1050 1200 1350 1500 900 1050 1200 1350 1500 WB (°F) 75°F Total Total2 Cap.1 Input (MBH) (kW) 85°F Sensible Capacity (MBH)1 Return Dry Bulb (°F) Total Total2 Cap.
036-21687-002-A-1105 TABLE 17: DJ048 COOLING CAPACITIES (4 TON) Temperature of Air on Condenser Coil Air on Evaporator Coil CFM 1200 1400 1600 1800 2000 1200 1400 1600 1800 2000 1200 1400 1600 1800 2000 WB (°F) 75°F Total Total2 Cap.1 Input (MBH) (kW) 85°F Sensible Capacity (MBH)1 Return Dry Bulb (°F) Total Total2 Cap.
036-21687-002-A-1105 TABLE 18: DJ060 COOLING CAPACITIES (5 TON) Temperature of Air on Condenser Coil Air on Evaporator Coil CFM 1600 1800 2000 2250 2500 1600 1800 2000 2250 2500 1600 1800 2000 2250 2500 WB (°F) 75°F Total Total2 Cap.1 Input (MBH) (kW) 85°F Sensible Capacity (MBH)1 Return Dry Bulb (°F) Total Total2 Cap.
036-21687-002-A-1105 TABLE 19: SUPPLY AIR BLOWER PERFORMANCE (DJ036 BELT DRIVE) - SIDE DUCT APPLICATION AVAILABLE EXTERNAL STATIC PRESSURE - IWG1 AIR FLOW CFM RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS 800 ---- ---- ---- ---- ---- ---- 696 357 0.38 743 389 0.42 786 422 0.45 900 ---- ---- ---- 656 353 0.38 706 385 0.41 753 417 0.45 797 450 0.48 0.2 0.3 0.4 0.5 0.6 BHP 1000 ---- ---- ---- 671 376 0.40 722 408 0.
036-21687-002-A-1105 TABLE 20: SUPPLY AIR BLOWER PERFORMANCE (DJ036 BELT DRIVE) - BOTTOM DUCT APPLICATION AVAILABLE EXTERNAL STATIC PRESSURE - IWG1 AIR FLOW CFM RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS 800 ---- ---- ---- ---- ---- ---- ---- ---- ---- 749 384 0.41 791 422 0.45 900 ---- ---- ---- ---- ---- ---- 720 364 0.39 764 404 0.43 806 443 0.47 0.2 0.3 0.4 0.5 0.6 BHP 1000 ---- ---- ---- 690 346 0.37 739 388 0.
036-21687-002-A-1105 TABLE 21: SUPPLY AIR BLOWER PERFORMANCE (DJ048 BELT DRIVE) - SIDE DUCT APPLICATION AVAILABLE EXTERNAL STATIC PRESSURE - IWG1 AIR FLOW 0.2 0.3 0.4 0.5 0.6 0.7 CFM RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP 1000 ---- ---- ---- ---- ---- ---- ---- ---- ---- 789 527 0.57 831 567 0.61 874 602 0.65 1100 ---- ---- ---- ---- ---- ---- ---- ---- ---- 811 559 0.60 854 599 0.64 896 634 0.
036-21687-002-A-1105 TABLE 22: SUPPLY AIR BLOWER PERFORMANCE (DJ048 BELT DRIVE) - BOTTOM DUCT APPLICATION AVAILABLE EXTERNAL STATIC PRESSURE - IWG1 AIR FLOW 0.2 0.3 0.4 0.5 0.6 0.7 CFM RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP 1000 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 833 564 0.61 879 605 0.65 1100 ---- ---- ---- ---- ---- ---- ---- ---- ---- 809 549 0.59 854 592 0.63 900 633 0.
036-21687-002-A-1105 TABLE 23: SUPPLY AIR BLOWER PERFORMANCE (DJ060 BELT DRIVE) - SIDE DUCT APPLICATION AVAILABLE EXTERNAL STATIC PRESSURE - IWG1 AIR FLOW 0.2 0.3 0.4 0.5 0.6 0.7 CFM RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP 1200 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 876 632 0.68 918 667 0.72 1300 ---- ---- ---- ---- ---- ---- ---- ---- ---- 855 628 0.67 898 668 0.72 940 703 0.
036-21687-002-A-1105 TABLE 24: SUPPLY AIR BLOWER PERFORMANCE (DJ060 BELT DRIVE) - BOTTOM DUCT APPLICATION AVAILABLE EXTERNAL STATIC PRESSURE - IWG1 AIR FLOW 0.2 0.3 0.4 0.5 0.6 0.7 CFM RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP 1000 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 862 453 0.49 901 498 0.53 1100 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 883 494 0.53 922 539 0.
036-21687-002-A-1105 TABLE 25: BELT DRIVE BLOWER MOTOR AND DRIVE DATA MODEL SIZE BLOWER RANGE (RPM) MOTOR1 HP FRAME ADJUSTABLE MOTOR PULLEY OUTSIDE DIA. (IN.) DESIGNATION PITCH DIA. (IN.) BELT (NOTCHED) FIXED BLOWER PULLEY BORE (IN.) DESIGNATION OUTSIDE DIA. (IN.) PITCH DIA. (IN.) BORE (IN.) DESIGNATION PITCH LENGTH (IN.) QTY. DJ036 600/920 1-1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK74 7.2 7.0 1 A39 40.3 1 DJ048 790/1120 1-1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK61 5.9 5.
036-21687-002-A-1105 TABLE 28: ELECTRICAL DATA - DJ036, 048 & 060 BELT DRIVE W/O POWERED CONVENIENCE OUTLET COMPRESSORS MODEL TONNAGE VOLTAGE RLA EACH LRA EACH OD FAN MOTOR FLA ID BLOWER MOTOR FLA CONV OUTLET FLA 208-1-60 11.3 68.0 2.3 7.6 0.0 230-1-60 11.3 68.0 2.3 7.6 0.0 208-3-60 8.3 68.0 2.3 5.2 0.0 230-3-60 8.3 68.0 2.3 5.2 0.0 460-3-60 5.1 34.0 1.3 2.6 0.0 575-3-60 3.2 26.0 1.3 2.0 0.0 208-1-60 15.4 86.0 2.3 7.6 0.0 230-1-60 15.4 86.0 2.3 7.6 0.
036-21687-002-A-1105 TABLE 28: ELECTRICAL DATA - DJ036, 048 & 060 BELT DRIVE W/O POWERED CONVENIENCE OUTLET (CONT) COMPRESSORS MODEL TONNAGE VOLTAGE RLA EACH LRA EACH OD FAN MOTOR FLA ID BLOWER MOTOR FLA CONV OUTLET FLA 208-1-60 25.0 150.0 2.3 7.6 0.0 230-1-60 25.0 150.0 2.3 7.6 0.0 208-3-60 17.3 123.0 2.3 5.2 0.0 230-3-60 17.3 123.0 2.3 5.2 0.0 460-3-60 8.4 70.0 1.3 2.6 0.0 575-3-60 7.0 53.0 1.3 2.0 0.0 DJ060 ELECTRIC HEATER HEATER HEATER MODEL NO.
036-21687-002-A-1105 TABLE 29: ELECTRICAL DATA - DJ036, 048 & 060 BELT DRIVE WITH POWERED CONVENIENCE OUTLET COMPRESSORS MODEL TONNAGE VOLTAGE RLA EACH LRA EACH OD FAN MOTOR FLA ID BLOWER MOTOR FLA CONV OUTLET FLA 208-1-60 11.3 68.0 2.3 7.6 10.0 230-1-60 11.3 68.0 2.3 7.6 10.0 208-3-60 8.3 68.0 2.3 5.2 10.0 230-3-60 8.3 68.0 2.3 5.2 10.0 460-3-60 5.1 34.0 1.3 2.6 5.0 575-3-60 3.2 26.0 1.3 2.0 4.0 208-1-60 15.4 86.0 2.3 7.6 10.0 230-1-60 15.4 86.0 2.3 7.
036-21687-002-A-1105 TABLE 29: ELECTRICAL DATA - DJ036, 048 & 060 BELT DRIVE WITH POWERED CONVENIENCE OUTLET (CONT) COMPRESSORS MODEL TONNAGE VOLTAGE RLA EACH LRA EACH OD FAN MOTOR FLA ID BLOWER MOTOR FLA CONV OUTLET FLA 208-1-60 25.0 150.0 2.3 7.6 10.0 230-1-60 25.0 150.0 2.3 7.6 10.0 208-3-60 17.3 123.0 2.3 5.2 10.0 230-3-60 17.3 123.0 2.3 5.2 10.0 460-3-60 8.4 70.0 1.3 2.6 5.0 575-3-60 7.0 53.0 1.3 2.0 4.0 DJ060 ELECTRIC HEATER HEATER HEATER MODEL NO.
036-21687-002-A-1105 TABLE 30: PHYSICAL DATA DJ MODELS EVAPORATOR BLOWER 036 048 060 Centrifugal Blower (Dia. x Wd. in.) 12 X 10 12 X 10 12 X 10 Fan Motor HP (Belt Drive) 1-1/2 1-1/2 1-1/2 Rows Deep 3 4 4 Fins Per Inch 13 13 13 Face Area (Sq. Ft.) 5.1 5.1 5.1 Propeller Dia. (in.) 24 24 24 Fan Motor Hp 1/2 1/2 1/2 4200 EVAPORATOR COIL CONDENSER FANS Nom. CFM 4200 4200 Rows Deep 2 2 2 Fins Per Inch 18 18 18 Face Area (Sq. Ft.) 17.1 17.1 17.
036-21687-002-A-1105 TYPICAL POWER WIRING REFER TO THE ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH, OVERCURRENT PROTECTION AND WIRING. TYPICAL CONTROL WIRING COOLING / HEATING (24 VOLT THERMOSTAT) COOLING ONLY (24 VOLT THERMOSTAT) THERMOSTAT 1 TERMINALS THERMOSTAT1 UNIT TERMINAL TERMINALS STRIP TB1 ADD JUMPER R RV UNIT TERMINAL STRIP TB1 RC R Y Y1 24 VOLT TRANSFORMER Y1 YC RH 24 VOLT TRANSFORMER Y2 Y2 W W1 G GF W2 C 1 G C 24 VOLT THERMOSTAT 2TH07701024.
036-21687-002-A-1105 FIGURE 3 - UNIT DIMENSIONS (3 - 5 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW FIGURE 4 - UNIT DIMENSIONS (3 - 5 TON COOLING/GAS HEAT) FRONT VIEW Unitary Products Group 37
036-21687-002-A-1105 DETAIL “A” FIGURE 5 - UNIT WITH ECONOMIZER RAINHOOD DETAIL “B” FIGURE 6 - 38 UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD Unitary Products Group
036-21687-002-A-1105 FIGURE 7 - UNIT DIMENSIONS (REAR VIEW) 1. Opening in the bottom to the unit can be located by the side in the insulation. 2. Do not remove the 2” knockout ring.
036-21687-002-A-1105 FIGURE 9 - 40 TYPICAL APPLICATIONS Unitary Products Group
036-21687-002-A-1105 BACK OF UNIT A 447/8 BACK OF UNIT A 447/8 821/4 821/4 D B F X X B APPROXIMATE CENTER OF GRAVITY CONDENSER COIL END OF UNIT C Y FRONT OF UNIT C E APPROXIMATE CENTER OF GRAVITY CONDENSER COIL END OF UNIT D Y FRONT OF UNIT FIGURE 10 - FOUR AND SIX POINT LOADING TABLE 35: DJ 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION UNIT TOTAL 4-Point Loading (lb) 6-Point Loading (lb) A B C D A B C D E F DJ036 Cooling/ Electric 575 132 125 155 164 89 85 82 102 106
036-21687-002-A-1105 TABLE 37: OPERATING WEIGHTS (LBS.) MODEL SIZE 3 TON 4 TON 5 TON 575 585 590 N04 615 - - N06 - 635 - N08 635 - 650 DJ (Cooling Only) BASIC UNIT DJ (Gas/Electric) N10 - 655 660 D06 625 635 640 D10 645 655 660 Economizer 50 Motorized Damper OPTIONS Electric Heater 26 5 - 7 kW 18 10 - 15 kW 23 20 - 30 kW ACCY.
036-21687-002-A-1105 GUIDE SPECIFICATIONS GENERAL Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. York's Sunline Magnum™ units are convertible single package units. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof.
036-21687-002-A-1105 brazed. Special Phenolic coating shall be available as a factory option. b. Evaporator and Condenser coils shall be of the direct expansion, draw-thru, design. Refrigerant Circuit and Refrigerant Safety Components shall include: a. Independent fixed-orifice or thermally operated expansion devices. b. Filter drier/strainer to eliminate any moisture or foreign matter. c.
036-21687-002-A-1105 OPTIONAL OUTDOOR AIR (Shall be made available by either/or): • • ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER- Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG.
036-21687-002-A-1105 46 Unitary Products Group
036-21687-002-A-1105 Unitary Products Group 47
Subject to change without notice. Printed in U.S.A. Copyright © 2005 by Unitary Products Group. All rights reserved.