Technical Guide

718432-YTG-A-0811
Johnson Controls Unitary Products 21
Additional Static Resistance
Size
(Tons)
Model CFM Wet Indoor Coil Economizer
1
1. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Filter/Frame Kit Electric Heat
024
(2.0)
DEZ
500 0.01 0.00 0.01 0.02
600 0.01 0.00 0.02 0.03
700 0.01 0.00 0.02 0.03
800 0.01 0.01 0.02 0.03
900 0.01 0.01 0.02 0.04
1000 0.02 0.01 0.02 0.04
1100 0.03 0.01 0.03 0.05
1200 0.04 0.02 0.03 0.06
030
(2.5)
DEZ
700 0.01 0.00 0.02 0.03
800 0.01 0.01 0.02 0.03
900 0.01 0.01 0.02 0.04
1000 0.02 0.01 0.02 0.04
1100 0.03 0.01 0.03 0.05
1200 0.04 0.02 0.03 0.06
1300 0.07 0.03 0.17 -
036
(3.0)
DEZ
700 0.01 0.00 0.02 0.03
800 0.01 0.01 0.02 0.03
900 0.01 0.01 0.02 0.04
1000 0.02 0.01 0.02 0.04
1100 0.03 0.01 0.03 0.05
1200 0.04 0.02 0.03 0.06
1300 0.04 0.03 0.03 0.07
1400 0.04 0.04 0.03 0.08
042
(3.5)
DEZ
1100 0.03 0.01 0.03 0.05
1200 0.04 0.02 0.03 0.06
1300 0.04 0.03 0.03 0.07
1400 0.04 0.04 0.03 0.08
1500 0.05 0.05 0.04 0.09
1600 0.06 0.06 0.05 0.10
048
(4.0)
DEZ
1100 0.03 0.01 0.03 0.05
1200 0.04 0.02 0.03 0.06
1300 0.04 0.03 0.03 0.07
1400 0.04 0.04 0.03 0.08
1500 0.04 0.05 0.04 0.09
1600 0.04 0.06 0.05 0.10
1700 0.05 0.07 0.05 0.11
1800 0.05 0.07 0.06 0.11
1900 0.06 0.08 0.06 0.11
2000 0.07 0.08 0.07 0.12
060
(5.0)
DEZ
1100 0.03 0.01 0.03 0.05
1200 0.04 0.02 0.03 0.06
1300 0.04 0.03 0.03 0.07
1400 0.04 0.04 0.03 0.08
1500 0.04 0.05 0.04 0.09
1600 0.04 0.06 0.05 0.10
1700 0.05 0.07 0.05 0.11
1800 0.05 0.07 0.06 0.11
1900 0.06 0.08 0.06 0.11
2000 0.07 0.08 0.07 0.12