Technical Guide
718432-YTG-D-0313
44 Johnson Controls Unitary Products
DEZ/DEQ Additional Static Resistance
Size
(Tons)
CFM Wet Indoor Coil Economizer
1
1. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance
of the return air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Filter/Frame Kit Electric Heat
DEZ/DEQ
024
(2.0)
500 0.01 0.00 0.01 0.02
600 0.01 0.00 0.02 0.03
700 0.01 0.00 0.02 0.03
800 0.01 0.01 0.02 0.03
900 0.01 0.01 0.02 0.04
1000 0.02 0.01 0.02 0.04
1100 0.03 0.01 0.03 0.05
1200 0.04 0.02 0.03 0.06
DEZ/DEQ
030
(2.5)
700 0.01 0.00 0.02 0.03
800 0.01 0.01 0.02 0.03
900 0.01 0.01 0.02 0.04
1000 0.02 0.01 0.02 0.04
1100 0.03 0.01 0.03 0.05
1200 0.04 0.02 0.03 0.06
1300 0.07 0.03 0.17 -
DEZ/DEQ
036
(3.0)
700 0.01 0.00 0.02 0.03
800 0.01 0.01 0.02 0.03
900 0.01 0.01 0.02 0.04
1000 0.02 0.01 0.02 0.04
1100 0.03 0.01 0.03 0.05
1200 0.04 0.02 0.03 0.06
1300 0.04 0.03 0.03 0.07
1400 0.04 0.04 0.03 0.08
DEZ/DEQ
042
(3.5)
1100 0.03 0.01 0.03 0.05
1200 0.04 0.02 0.03 0.06
1300 0.04 0.03 0.03 0.07
1400 0.04 0.04 0.03 0.08
1500 0.04 0.05 0.04 0.09
1600 0.04 0.06 0.05 0.10
1700 0.05 0.07 0.05 0.11
1800 0.05 0.07 0.06 0.11
1900 0.06 0.08 0.06 0.11
2000 0.07 0.08 0.07 0.12
DEZ/DEQ
048
(4.0)
1100 0.03 0.01 0.03 0.05
1200 0.04 0.02 0.03 0.06
1300 0.04 0.03 0.03 0.07
1400 0.04 0.04 0.03 0.08
1500 0.04 0.05 0.04 0.09
1600 0.04 0.06 0.05 0.10
1700 0.05 0.07 0.05 0.11
1800 0.05 0.07 0.06 0.11
1900 0.06 0.08 0.06 0.11
2000 0.07 0.08 0.07 0.12
DEZ/DEQ
060
(5.0)
1100 0.03 0.01 0.03 0.05
1200 0.04 0.02 0.03 0.06
1300 0.04 0.03 0.03 0.07
1400 0.04 0.04 0.03 0.08
1500 0.04 0.05 0.04 0.09
1600 0.04 0.06 0.05 0.10
1700 0.05 0.07 0.05 0.11
1800 0.05 0.07 0.06 0.11
1900 0.06 0.08 0.06 0.11
2000 0.07 0.08 0.07 0.12