Technical Guide
718432-YTG-D-0313
Johnson Controls Unitary Products 15
115°F 125°F
900
77 33.4 3.4 16.4 13.1 9.9 - - - 30.4 3.6 17.0 12.0 8.7 - - -
72 29.9 3.3 21.4 18.2 15.0 11.7 - - 26.8 3.5 20.1 16.8 13.6 10.3 - -
67 26.4 3.2 26.4 23.2 20.0 16.8 13.6 - 23.2 3.4 23.2 21.7 18.5 15.2 11.9 -
62 25.3 3.2 25.3 25.3 22.9 19.6 16.4 13.2 22.3 3.4 22.3 22.3 19.9 16.6 13.3 10.1
57 25.2 3.2 25.2 25.2 22.8 19.6 16.3 13.1 22.3 3.4 22.3 22.3 19.6 16.4 13.1 9.8
1050
77 34.2 3.5 19.8 14.3 10.7 - - - 31.2 3.7 20.8 14.1 9.5 - - -
72 30.7 3.4 23.4 19.8 16.2 12.5 - - 27.5 3.6 22.3 18.6 14.9 11.1 - -
67 27.1 3.3 27.1 25.3 21.6 18.0 14.4 - 23.8 3.5 23.8 23.8 20.2 16.5 12.8 -
62 25.9 3.3 25.9 25.9 24.7 21.1 17.4 13.8 22.9 3.5 22.9 22.9 21.8 18.1 14.3 10.6
57 25.8 3.3 25.8 25.8 24.6 21.0 17.4 13.7 22.8 3.5 22.8 22.8 21.5 17.8 14.1 10.4
1200
77 35.1 3.6 23.2 15.6 11.5 - - - 32.0 3.9 24.6 16.2 10.4 - - -
72 31.4 3.5 25.5 21.4 17.4 13.3 - - 28.2 3.7 24.5 20.3 16.1 12.0 - -
67 27.8 3.4 27.8 27.3 23.2 19.2 15.1 - 24.4 3.6 24.4 24.4 21.9 17.8 13.6 -
62 26.5 3.4 26.5 26.5 26.5 22.5 18.4 14.4 23.5 3.6 23.5 23.5 23.5 19.5 15.4 11.2
57 26.5 3.4 26.5 26.5 26.5 22.4 18.4 14.3 23.4 3.6 23.4 23.4 23.4 19.3 15.1 10.9
1300
72 31.4 3.6 26.4 22.1 17.8 13.5 - - 28.1 3.8 25.4 21.0 16.6 12.2 - -
67 27.7 3.5 27.7 27.5 23.8 19.5 15.2 - 24.3 3.7 24.3 24.3 22.5 18.1 13.7 -
62 26.5 3.5 26.5 26.5 26.5 22.2 17.9 13.6 23.4 3.7 23.4 23.4 23.4 19.1 14.7 10.3
57 26.4 3.5 26.4 26.4 26.4 22.1 17.8 13.5 23.4 3.7 23.4 23.4 23.4 18.9 14.5 10.1
1400
72 31.4 3.7 27.4 22.8 18.3 13.7 - - 28.0 3.9 26.4 21.7 17.0 12.3 - -
67 27.7 3.6 27.7 27.7 24.4 19.9 15.3 - 24.2 3.8 24.2 24.2 23.1 18.4 13.8 -
62 26.5 3.6 26.5 26.5 26.5 21.9 17.4 12.8 23.4 3.8 23.4 23.4 23.4 18.7 14.0 9.3
57 26.4 3.6 26.4 26.4 26.4 21.9 17.3 12.7 23.3 3.8 23.3 23.3 23.3 18.6 13.9 9.2
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
DEZ036 (3.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65