Technical Guide
294604-YTG-B-0508
52 Johnson Controls Unitary Products
060
(5.0)
208/230-1-60 26.2 150 41 2.8 9.1
None - - - 44.7 60
2NH04501006 7.5 / 10 2 36.1 / 41.7 56.5 / 63.5 70 / 70
2NH04501506 11.3 / 15 2 54.2 / 62.5 79.1 / 89.5 80 / 90
2NH04502006 15 / 20 2 72.2 / 83.3 101.7 / 115.5 110 / 125
2NH04502506 18.8 / 25 2 90.3 / 104.2 124.2 / 141.6 125 / 150
208/230-3-60 17.9 120 28 2.8 9.1
None - - - 34.3 45
2NH04501025 7.5 / 10 1 20.8 / 24.1 37.4 / 41.4 45 / 50
2NH04501525 11.3 / 15 1 31.3 / 36.1 50.5 / 56.5 60 / 60
2NH04502025 15 / 20 2 41.7 / 48.1 63.5 / 71.5 70 / 80
2NH04502525 18.8 / 25 2 52.1 / 60.1 76.5 / 86.6 80 / 90
460-3-60 8.3 70 13 1.4 4.6
None - - - 16.4 20
2NH04501046 10 1 12 20.8 25
2NH04501546 15 1 18 28.3 30
2NH04502046 20 2 24.1 35.8 40
2NH04502546 25 2 30.1 43.3 45
575-3-60 7.4 53 12 1.1 3.6
None - - - 14 20
2NH04501058 10 1 9.6 16.5 20
2NH04501558 15 1 14.4 22.5 25
2NH04502058 20 2 19.2 28.6 30
2NH04502558 25 2 24.1 34.6 35
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
DEX024-048 Cooling Only With/Without Electric Heat
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA Model kW Stages Amps
024
(2.0)
208/230-1-60 10.2 52 16 1.2 4.3
None - - - 18.3 25
2NH04500506 3.8/5 1 18.1/20.8 27.9 / 31.4 30 / 35
2NH04500706 5.6/7.5 2 27.1/31.3 39.2 / 44.4 40 / 45
2NH04501006 7.5/10 2 36.1/41.7 50.5 / 57.5 60 / 60
030
(2.5)
208/230-1-60 14.1 70 22 1.2 4.3
None - - - 23.1 30
2NH04500506 3.8/5 1 18.1/20.8 27.9 / 31.4 35 / 35
2NH04500706 5.6/7.5 2 27.1/31.3 39.2 / 44.4 40 / 45
2NH04501006 7.5/10 2 36.1/41.7 50.5 / 57.5 60 / 60
2NH04501506 11.3/15 2 54.2/62.5 73.1 / 83.5 80 / 90
036
(3.0)
208/230-1-60 16.6 82 26 1.2 4.3
None - - - 26.3 35
2NH04500506 3.8/5 1 18.1/20.8 27.9 / 31.4 35 / 40
2NH04500706 5.6/7.5 2 27.1/31.3 39.2 / 44.4 40 / 45
2NH04501006 7.5/10 2 36.1/41.7 50.5 / 57.5 60 / 60
2NH04501506 11.3/15 2 54.2/62.5 73.1 / 83.5 80 / 90
208/230-3-60 11.1 58 17 1.2 4.3
None - - - 19.4 25
2NH04501025 7.5/10 1 20.8/24.1 31.4 / 35.4 35 / 40
2NH04501525 11.3/15 1 31.3/36.1 44.5 / 50.5 45 / 60
460-3-60 4.5 29 7 0.8 4.3
None - - - 10.7 15
2NH04501046 10 1 12 20.4 25
2NH04501546 15 1 18 27.9 30
042
(3.5)
208/230-1-60 16.6 96 26 1.4 6.8
None - - - 29 35
2NH04500506 3.8/5 1 18.1/20.8 31.1 / 34.5 40 / 45
2NH04500706 5.6/7.5 2 27.1/31.3 42.4 / 47.6 45 / 50
2NH04501006 7.5/10 2 36.1/41.7 53.6 / 60.6 60 / 70
2NH04501506 11.3/15 2 54.2/62.5 76.2 / 86.6 80 / 90
208/230-3-60 13.4 88 21 1.4 6.8
None - - - 25 30
2NH04501025 7.5/10 1 20.8/24.1 34.6 / 38.6 35 / 40
2NH04501525 11.3/15 1 31.3/36.1 47.6 / 53.6 50 / 60
460-3-60 6.1 44 10 0.8 6.8
None - - - 15.4 20
2NH04501046 10 1 12 23.5 25
2NH04501546 15 1 18 31.1 35
DEQ024-060 Cooling Only With/Without Electric Heat (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA Model kW Stages Amps