Technical Guide
294604-YTG-B-0508
50 Johnson Controls Unitary Products
060
(5.0)
208/230-1-60 26.2 150 41 1.7 7.6
None - - - 42.1 60
2NH04501006 7.5 / 10 2 36.1 / 41.7 54.6 / 61.6 60 / 70
2NH04501506 11.3 / 15 2 54.2 / 62.5 77.2 / 87.6 80 / 90
2NH04502006 15 / 20 2 72.2 / 83.3 99.8 / 113.7 100 / 125
2NH04502506 18.8 / 25 2 90.3 / 104.2 122.3 / 139.7 125 / 150
208/230-3-60 17.9 120 28 1.7 7.6
None - - - 31.7 40
2NH04501025 7.5 / 10 1 20.8 / 24.1 35.6 / 39.6 45 / 45
2NH04501525 11.3 / 15 1 31.3 / 36.1 48.6 / 54.6 50 / 60
2NH04502025 15 / 20 2 41.7 / 48.1 61.6 / 69.6 70 / 70
2NH04502525 18.8 / 25 2 52.1 / 60.1 74.7 / 84.7 80 / 90
460-3-60 9.6 70 15 1.0 3.8
None - - - 16.8 25
2NH04501046 10 1 12 19.8 25
2NH04501546 15 1 18 27.3 30
2NH04502046 20 2 24.1 34.8 35
2NH04502546 25 2 30.1 42.3 45
575-3-60 7.4 53 12 0.8 3.0
None - - - 13.1 20
2NH04501058 10 1 9.6 15.8 20
2NH04501558 15 1 14.4 21.8 25
2NH04502058 20 2 19.2 27.8 30
2NH04502558 25 2 24.1 33.8 35
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
DEZ024-060 Cooling Only With/Without Electric Heat (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA Model kW Stages Amps