Technical Guide
294604-YTG-B-0508
18 Johnson Controls Unitary Products
115°F 125°F
1050
77 38.7 4.4 19.0 14.6 10.3 - - - 35.0 4.8 17.6 13.3 8.9 - - -
72 35.8 4.3 25.9 21.5 17.2 12.8 - - 32.3 4.7 24.6 20.2 15.8 11.5 - -
67 33.0 4.3 32.8 28.5 24.1 19.7 15.3 - 29.7 4.7 29.7 27.1 22.8 18.4 14.1 -
62 31.7 4.3 31.7 31.7 28.2 23.8 19.4 15.0 29.6 4.7 29.6 29.6 26.1 21.8 17.4 13.1
57 31.6 4.2 31.6 31.6 28.0 23.6 19.3 14.9 28.9 4.6 28.9 28.9 25.4 21.0 16.7 12.3
1225
77 39.3 4.5 23.6 16.1 11.1 - - - 35.4 4.9 23.2 14.6 9.7 - - -
72 36.4 4.4 28.5 23.6 18.7 13.7 - - 32.7 4.8 27.1 22.2 17.3 12.4 - -
67 33.5 4.4 33.4 31.1 26.2 21.2 16.3 - 30.0 4.8 30.0 29.7 24.8 19.9 15.0 -
62 32.2 4.4 32.2 32.2 30.6 25.7 20.7 15.8 29.9 4.8 29.9 29.9 28.5 23.7 18.7 13.8
57 32.1 4.3 32.1 32.1 30.5 25.5 20.6 15.7 29.2 4.7 29.2 29.2 27.7 22.9 17.9 13.0
1400
77 39.9 4.6 28.2 17.5 12.0 - - - 35.8 5.0 28.8 16.0 10.5 - - -
72 37.0 4.6 31.1 25.6 20.1 14.7 - - 33.0 5.0 29.6 24.1 18.7 13.2 - -
67 34.1 4.5 34.1 33.7 28.3 22.8 17.3 - 30.3 4.9 30.3 30.3 26.8 21.4 15.9 -
62 32.8 4.5 32.8 32.8 33.1 27.6 22.1 16.6 30.2 4.9 30.2 30.2 30.2 25.6 19.9 14.5
57 32.6 4.5 32.6 32.6 32.9 27.4 21.9 16.4 29.5 4.9 29.5 29.5 29.5 24.8 19.0 13.6
1575
72 36.7 4.7 33.1 27.1 21.2 15.3 - - 32.6 5.1 31.3 25.5 19.6 13.8 - -
67 33.8 4.7 33.8 33.6 29.8 23.8 17.9 - 29.9 5.1 29.9 29.9 28.2 22.3 16.5 -
62 32.5 4.6 32.5 32.5 32.6 26.7 20.8 14.9 29.8 5.0 29.8 29.8 29.8 24.4 18.4 12.5
57 32.3 4.6 32.3 32.3 32.5 26.5 20.6 14.7 29.1 5.0 29.1 29.1 29.1 23.6 17.6 11.7
1750
72 36.4 4.9 35.0 28.6 22.3 15.9 - - 32.1 5.3 32.1 26.8 20.6 14.3 - -
67 33.5 4.8 33.5 33.5 31.3 24.9 18.6 - 29.5 5.2 29.5 29.5 29.5 23.3 17.0 -
62 32.2 4.8 32.2 32.2 32.2 25.9 19.5 13.1 29.4 5.2 29.4 29.4 29.4 23.1 16.9 10.6
57 32.0 4.7 32.0 32.0 32.0 25.7 19.3 13.0 28.7 5.2 28.7 28.7 28.7 22.4 16.2 9.9
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
DEZ042 (3.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65