Technical Guide
294604-YTG-G-0511
22 Johnson Controls Unitary Products
115°F 125°F
1500
77 59.3 6.7 27.4 21.9 16.4 - - - 54.7 7.3 25.1 19.7 14.4 - - -
72 52.9 6.6 35.4 29.9 24.4 18.9 - - 48.2 7.1 33.0 27.6 22.3 16.9 - -
67 46.5 6.4 43.4 37.9 32.4 27.0 21.5 - 41.7 7.0 40.9 35.5 30.2 24.8 19.5 -
62 41.1 6.3 41.1 41.1 39.8 34.3 28.9 23.4 36.3 6.8 36.3 36.3 36.3 31.5 26.2 20.8
57 42.5 6.3 42.5 42.5 41.1 35.6 30.1 24.6 39.0 6.9 39.0 39.0 37.9 32.6 27.2 21.9
1550
77 60.0 6.7 28.2 22.5 16.8 - - - 55.3 7.3 26.4 20.4 14.8 - - -
72 53.5 6.5 36.4 30.8 25.1 19.4 - - 48.7 7.1 34.0 28.5 22.9 17.3 - -
67 47.0 6.4 44.7 39.0 33.3 27.7 22.0 - 42.1 7.0 42.1 36.6 31.0 25.4 19.8 -
62 41.6 6.3 41.6 41.6 40.9 35.2 29.6 23.9 36.7 6.8 36.7 36.7 36.7 32.2 26.7 21.1
57 42.9 6.3 42.9 42.9 42.2 36.5 30.9 25.2 39.4 6.9 39.4 39.4 38.9 33.3 27.8 22.2
1600
77 60.6 6.7 29.0 23.2 17.3 - - - 55.8 7.2 27.7 21.0 15.1 - - -
72 54.1 6.5 37.5 31.6 25.8 19.9 - - 49.2 7.1 35.1 29.3 23.5 17.6 - -
67 47.5 6.4 46.0 40.1 34.2 28.4 22.5 - 42.5 6.9 42.5 37.6 31.8 26.0 20.1 -
62 42.0 6.2 42.0 42.0 42.0 36.1 30.3 24.4 37.0 6.8 37.0 37.0 37.0 33.0 27.2 21.3
57 43.4 6.2 43.4 43.4 43.3 37.5 31.6 25.7 39.8 6.8 39.8 39.8 39.8 34.1 28.3 22.5
1800
72 54.3 6.7 39.8 33.4 27.0 20.6 - - 49.1 7.3 37.2 30.9 24.6 18.3 - -
67 47.7 6.5 46.9 42.2 35.8 29.4 23.0 - 42.5 7.1 42.5 39.6 33.3 27.0 20.7 -
62 42.2 6.4 42.2 42.2 42.2 35.8 29.4 23.0 37.0 7.0 37.0 37.0 37.0 31.7 25.4 19.2
57 43.5 6.4 43.5 43.5 43.5 37.1 30.7 24.3 39.7 7.0 39.7 39.7 39.7 33.5 27.3 21.0
2000
72 54.5 6.9 42.0 35.1 28.2 21.2 - - 49.1 7.4 39.3 32.5 25.8 19.0 - -
67 47.9 6.7 47.9 44.4 37.4 30.5 23.5 - 42.5 7.3 42.5 41.6 34.9 28.1 21.4 -
62 42.3 6.6 42.3 42.3 42.3 35.4 28.5 21.5 37.0 7.1 37.0 37.0 37.0 30.5 23.7 17.0
57 43.7 6.6 43.7 43.7 43.7 36.8 29.8 22.9 39.7 7.2 39.7 39.7 39.7 33.0 26.2 19.5
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
DEZ060 (5.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65