Technical Guide
718432-YTG-E-0314
Johnson Controls Unitary Products 9
DEZ/DEQ Unit Limitations
Model
(Tons)
Unit Voltage
Unit Limitations
Applied Voltage Outdoor DB Temp
Min Max Max (°F)
DEZ/DEQ 024
(2.0)
208/230-1-60 187 252 125
DEZ/DEQ 030
(2.5)
208/230-1-60 187 252 125
DEZ/DEQ 036
(3.0)
208/230-1-60 187 252 125
208/230-3-60 187 252 125
460-3-60 432 504 125
DEZ/DEQ 042
(3.5)
208/230-1-60 187 252 125
208/230-3-60 187 252 125
460-3-60 432 504 125
DEZ/DEQ 048
(4.0)
208/230-1-60 187 252 115
208/230-3-60 187 252 115
460-3-60 432 504 115
DEZ/DEQ 060
(5.0)
208/230-1-60 187 252 115
208/230-3-60 187 252 115
460-3-60 432 504 115
DEX Unit Limitations
Model
(Tons)
Unit Voltage
Unit Limitations
Applied Voltage Outdoor DB Temp
Min Max Max (°F)
DEX024
(2.0)
208/230-1-60 187 252 115
DEX030
(2.5)
208/230-1-60 187 252 115
DEX036
(3.0)
208/230-1-60 187 252 115
208/230-3-60 187 252 115
460-3-60 432 504 115
DEX042
(3.5)
208/230-1-60 187 252 115
208/230-3-60 187 252 115
460-3-60 432 504 115
DEX048
(4.0)
208/230-1-60 187 252 115
208/230-3-60 187 252 115
460-3-60 432 504 115