Technical Guide

718432-YTG-E-0314
Johnson Controls Unitary Products 21
115°F 125°F
1500
77 53.5 5.4 29.5 22.1 16.0 - - - 48.7 5.8 29.5 18.7 12.5 - - -
72 48.8 5.4 36.8 30.7 24.6 18.5 - - 44.0 5.9 34.4 28.2 22.0 15.7 - -
67 44.1 5.4 44.1 39.3 33.2 27.1 21.1 - 39.4 5.9 39.4 37.7 31.4 25.2 18.9 -
62 42.6 5.3 42.6 42.6 37.5 31.4 25.3 19.2 38.7 5.8 38.7 38.7 32.6 26.4 20.2 13.9
57 43.2 5.3 43.2 42.9 36.9 30.8 24.7 18.6 40.0 5.8 40.0 39.6 32.0 25.8 19.5 13.3
1625
77 54.9 5.4 34.3 23.9 17.4 - - - 50.4 5.8 35.2 22.7 14.2 - - -
72 50.1 5.4 39.8 33.3 26.7 20.2 - - 45.6 5.9 38.0 31.3 24.6 17.9 - -
67 45.3 5.4 45.3 42.6 36.1 29.6 23.1 - 40.8 5.9 40.8 40.8 35.1 28.4 21.7 -
62 43.7 5.3 43.7 43.7 40.7 34.2 27.7 21.1 40.1 5.8 40.1 40.1 36.7 30.0 23.3 16.6
57 44.4 5.3 44.4 44.3 40.0 33.5 27.0 20.5 41.4 5.8 41.4 41.2 36.0 29.3 22.6 15.9
1750
77 56.4 5.4 39.0 25.7 18.8 - - - 52.1 5.8 40.9 26.6 15.8 - - -
72 51.4 5.4 42.8 35.8 28.9 21.9 - - 47.1 5.9 41.5 34.4 27.3 20.2 - -
67 46.5 5.4 46.5 45.9 39.0 32.0 25.1 - 42.2 5.9 42.2 42.2 38.7 31.6 24.5 -
62 44.9 5.3 44.9 44.9 43.9 37.0 30.0 23.1 41.4 5.8 41.4 41.4 40.7 33.6 26.4 19.3
57 45.6 5.3 45.6 45.6 43.2 36.3 29.3 22.4 42.8 5.8 42.8 42.8 39.9 32.8 25.7 18.5
1875
72 51.6 5.4 43.6 36.3 29.0 21.7 - - 47.3 5.9 42.2 34.6 27.1 19.5 - -
67 46.6 5.4 46.6 46.3 39.1 31.8 24.5 - 42.3 5.9 42.3 42.3 38.5 30.9 23.4 -
62 45.0 5.3 45.0 45.0 44.1 36.8 29.5 22.2 41.6 5.8 41.6 41.6 40.6 33.1 25.5 18.0
57 45.7 5.3 45.7 45.7 43.4 36.1 28.8 21.5 43.0 5.8 43.0 43.0 39.9 32.3 24.8 17.2
2000
72 51.7 5.4 44.4 36.8 29.1 21.5 - - 47.5 5.9 42.8 34.8 26.9 18.9 - -
67 46.7 5.4 46.7 46.7 39.3 31.7 24.0 - 42.5 5.9 42.5 42.5 38.3 30.3 22.3 -
62 45.1 5.3 45.1 45.1 44.3 36.7 29.0 21.4 41.8 5.8 41.8 41.8 40.6 32.6 24.6 16.6
57 45.8 5.3 45.8 45.8 43.6 36.0 28.3 20.7 43.2 5.8 43.2 43.2 39.9 31.9 23.9 15.9
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
DEZ060 (5.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65