Technical Guide
294604-YTG-B-0508
22 Johnson Controls Unitary Products
115°F 125°F
1500
77 56.2 6.6 26.8 20.8 14.8 - - - 51.1 7.2 25.0 19.1 13.2 - - -
72 51.2 6.5 35.7 29.7 23.7 17.7 - - 46.3 7.1 33.8 27.9 22.0 16.0 - -
67 46.1 6.4 44.7 38.7 32.7 26.7 20.7 - 41.4 6.9 41.4 36.7 30.8 24.9 18.9 -
62 42.7 6.3 42.7 42.7 40.2 34.2 28.2 22.2 38.7 6.9 38.7 38.7 37.6 31.7 25.7 19.8
57 44.1 6.3 44.1 44.1 38.5 32.5 26.5 20.5 40.8 6.9 40.8 40.8 35.0 29.1 23.2 17.2
1675
77 57.3 6.5 31.3 22.5 15.9 - - - 52.0 7.2 30.6 20.8 14.2 - - -
72 52.2 6.4 38.8 32.2 25.5 18.9 - - 47.0 7.0 36.9 30.3 23.7 17.2 - -
67 47.0 6.3 46.3 41.8 35.2 28.5 21.9 - 42.1 6.9 42.1 39.8 33.2 26.6 20.1 -
62 43.5 6.3 43.5 43.5 43.2 36.6 30.0 23.3 39.3 6.8 39.3 39.3 39.3 34.2 27.4 20.9
57 45.0 6.3 45.0 45.0 41.4 34.8 28.1 21.5 41.5 6.9 41.5 41.5 37.8 31.4 24.7 18.1
1850
77 58.4 6.5 35.9 24.3 17.0 - - - 52.8 7.1 36.2 22.5 15.3 - - -
72 53.1 6.4 41.9 34.6 27.3 20.0 - - 47.8 6.9 39.9 32.7 25.5 18.3 - -
67 47.9 6.3 47.9 44.9 37.6 30.3 23.1 - 42.8 6.8 42.8 42.8 35.7 28.4 21.2 -
62 44.3 6.2 44.3 44.3 46.3 39.0 31.7 24.4 40.0 6.8 40.0 40.0 40.0 36.7 29.1 21.9
57 45.8 6.2 45.8 45.8 44.3 37.0 29.8 22.5 42.2 6.8 42.2 42.2 40.6 33.7 26.2 19.0
1925
72 53.7 6.5 43.0 35.6 28.1 20.6 - - 48.2 7.1 41.1 33.6 26.2 18.7 - -
67 48.3 6.4 48.3 46.1 38.7 31.2 23.7 - 43.2 6.9 43.2 43.2 36.7 29.2 21.8 -
62 44.8 6.3 44.8 44.8 45.7 38.2 30.8 23.3 40.3 6.9 40.3 40.3 40.3 34.8 27.2 19.8
57 46.3 6.4 46.3 46.3 45.5 38.0 30.5 23.0 42.5 6.9 42.5 42.5 41.8 34.5 26.9 19.4
2000
72 54.2 6.7 44.2 36.5 28.8 21.1 - - 48.6 7.3 42.3 34.6 26.9 19.2 - -
67 48.8 6.5 48.8 47.4 39.7 32.0 24.3 - 43.5 7.1 43.5 43.5 37.7 30.0 22.3 -
62 45.2 6.5 45.2 45.2 45.2 37.5 29.8 22.1 40.7 7.1 40.7 40.7 40.7 33.0 25.3 17.6
57 46.7 6.5 46.7 46.7 46.7 39.0 31.3 23.6 42.9 7.1 42.9 42.9 42.9 35.2 27.5 19.8
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
DEZ060 (5.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65