Specifications

JOHNSON CONTROLS
2-50
FORM 102.20-N1 (1109)
Installation
FIG. 2-72 – INTEGRAL FACE AND BYPASS COIL (HORIZONTAL; TUBES, STEAM SHOWN)
FACE
DAMPERS
CLOSED
BYPASS
OPEN
STEAM IN
ACTUATOR
STEAM OUT
LD09630
VIFB and IFB
A complete IOM is provided with each
IFB or VIFB coil unit.
VIFB lower header must be free to
oat. After coil has been piped, re-
move yellow colored bolts to allow
header to oat. Always “back up on
the coil connections when installing
ttings.
VIFB Warranty will be voided should
return piping on lower header (inlet
and return on two-row header) not
include exible connector(s) and if
lower header(s) bolts are not removed
prior to use.
See IFB/VIFB manufacturer's IOM
for additional piping details.
Factory does NOT pipe connections to
unit exterior.
Below 35°F, the Vertical Tube Integral Face and Bypass
(VIFB) or Integral Face and Bypass (IFB) operates
with full steam pressure or full water ow at all times.
This prevents freeze-up and temperature stratication.
FIG. 2-73 – VERTICAL INTEGRAL FACE AND
BYPASS COIL
STEAM IN
STEAM OUT
ACTUATOR
LD09631
(FACE MOUNTED ACTUATOR SHOWN)