Specifications
2-5
JOHNSON CONTROLS
FORM 102.20-N1 (1109)
2
Clearance
Allow sufcient space around the unit
for removing the access panels and
various parts of the unit. A minimum
clearance equal to the width of the
unit must be provided on one side of
the unit for removing the coil or fan
assembly.
Mounting
Units must be installed in such a manner as to provide
enough elevation for properly designed condensate
traps.
See Section 2 “Piping Connections - Condensate
Drain Trap.”
FIG. 2-3 – NO BASERAIL – HOUSEKEEPING PAD
REQUIRED TO ACCOMMODATE TRAP
HEIGHT
LD05372
Floor
The oor must be at and level.
Housekeeping Pad
The housekeeping pad must be at and level (see Fig's
2-3, 2-4 and 2-5).
FIG. 2-4 – NO HOUSEKEEPING PAD – BASERAIL
REQUIRED TO ACCOMMODATE TRAP
HEIGHT
LD05373
0
FIG. 2-5 – WITH BASERAIL AND HOUSEKEEPING
PAD
LD05374