Specifications
177008-YIM-A-0406
Unitary Products Group 29
ZJ060 (5.0 Ton) Blower Performance-Down Flow
Table 14: ZJ Blower Performance Side Flow
ZJ036 (3.0 Ton) Blower Performance-Side Flow
CFM RPM WATTS BHP CFM RPM WATTS BHP CFM RPM WATTS BHP CFM RPM WATTS BHP CFM RPM WATTS BHP CFM RPM WATTS BHP
0.2 2624 1171 1332 1.43 2390 1103 1133 1.22 2164 1035 957 1.03 1944 968 804 0.86 1731 901 674 0.72 1525 834 567 0.61
0.3 2483 1172 1296 1.39 2250 1104 1097 1.18 2024 1036 920 0.99 1804 969 767 0.82 1591 902 637 0.68 1385 835 531 0.57
0.4 2354 1173 1258 1.35 2121 1105 1058 1.14 1894 1038 882 0.95 1675 970 729 0.78 1462 903 599 0.64 1256 837 492 0.53
0.5 2233 1175 1217 1.31 2000 1107 1018 1.09 1773 1039 842 0.90 1554 972 689 0.74 1341 905 559 0.60 1135 838 452 0.49
0.6 2118 1176 1175 1.26 1884 1109 975 1.05 1658 1041 799 0.86 1438 974 646 0.69 1225 907 516 0.55 1019 840 409 0.44
0.7 2006 1178 1129 1.21 1772 1110 930 1.00 1546 1043 754 0.81 1326 975 601 0.64 1113 909 471 0.50 ---- ---- ---- ----
0.8 1894 1181 1080 1.16 1661 1113 881 0.94 1434 1045 704 0.76 1214 978 551 0.59 ---- ---- ---- ---- ---- ---- ---- ----
0.9 1780 1183 1027 1.10 1547 1115 828 0.89 1321 1047 652 0.70 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
1 1662 1185 970 1.04 1429 1117 771 0.83 1203 1050 595 0.64 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
1.1 1537 1188 909 0.97 1304 1120 710 0.76 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
1.2 1403 1191 842 0.90 1169 1123 643 0.69 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
1.3 1256 1194 771 0.83 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
1. External Static Pressure (ESP) is that available for supply and return duct system including internal losses from gas heat exchangers and 1" filters.
See STATIC RESISTANCE table for additional applications.
2. TURNS OPEN = Setting of the variable pitch motor sheave where "0 Turns Open" is fully closed.
ESP
1
TURNS OPEN
2
0 Turns Open 1 Turn Open 2 Turns Open 3 Turns Open 4 Turns Open 5 Turns Open
5 Ton Belt Drive Assembly With Factory Installed AK56 Blower Sheave And A36 Belt (Down Flow)
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1000 1200 1400 1600 1800 2000 2200 2400 2600 2800
CFM
ESP (IWG)
0 Turns4 Turns 3 Turns 2 Turns 1 Turn5 Turns
CFM RPM WATTS BHP CFM RPM WATTS BHP CFM RPM WATTS BHP CFM RPM WATTS BHP CFM RPM WATTS BHP CFM RPM WATTS BHP
0.2 1979 879 713 0.76 1811 830 635 0.68 1641 781 563 0.60 1468 731 496 0.53 1293 681 436 0.47 1116 630 382 0.41
0.3 1791 880 677 0.73 1623 831 599 0.64 1453 781 527 0.57 1280 732 461 0.49 1105 682 401 0.43 928 631 347 0.37
0.4 1619 881 635 0.68 1451 832 557 0.60 1281 782 485 0.52 1108 733 419 0.45 933 683 359 0.38 ---- ---- ---- ----
0.5 1446 882 590 0.63 1277 833 512 0.55 1107 784 440 0.47 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
0.6 1252 883 543 0.58 1084 834 465 0.50 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
0.7 1020 885 497 0.53 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
1. External Static Pressure (ESP) is that available for supply and return duct system including internal losses from gas heat exchangers and 1" filters.
See STATIC RESISTANCE table for additional applications.
2. TURNS OPEN = Setting of the variable pitch motor sheave where "0 Turns Open" is fully closed.
ESP
1
TURNS OPEN
2
0 Turns Open 1 Turn Open 2 Turns Open 3 Turns Open 4 Turns Open 5 Turns Open
3 Ton Belt Drive Assembly With Factory Installed AK74 Blower Sheave And A39 Belt (Side Flow)
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
800 1000 1200 1400 1600 1800 2000 2200
CFM
ESP (IWG)
0 Turns4 Turns 3 Turns 2 Turns 1 Turn5 Turns