Technical Guide
718419-YTG-F-0314
Johnson Controls Unitary Products 61
BHZ060
(5.0)
208/230-1-60 25.0 134 39 2.3 7.6
None --- --- --- 41.2 50
2NP04501006 7.5 / 10 2 36.1 / 41.7 86.3 / 93.2 100 / 100
2NP04501506 11.3 / 15 2 54.2 / 62.5 108.9 / 119.3 110 / 125
2NP04502006 15 / 20 2 72.2 / 83.3 131.4 / 145.3 150 / 150
2NP04502506 18.8 / 25 2 90.3 / 104.2 154 / 171.4 175 / 175
2NE04501006 7.5 / 10 2 36.1 / 41.7 45.1 / 51.2 50 / 60
2NE04501506 11.3 / 15 2 54.2 / 62.5 67.7 / 78.1 70 / 80
2NE04502006 15 / 20 2 72.2 / 83.3 90.3 / 104.2 100 / 110
2NE04502506 18.8 / 25 2 90.3 / 104.2 112.8 / 130.2 125 / 150
208/230-3-60 15.9 110 25 2.3 7.6
None --- --- --- 29.8 40
2NH04501025 7.5 / 10 1 20.8 / 24.1 55.8 / 59.8 60 / 60
2NH04501525 11.3 / 15 1 31.3 / 36.1 68.9 / 74.9 70 / 80
2NH04502025 15 / 20 2 41.7 / 48.1 81.9 / 89.9 90 / 90
2NH04502525 18.8 / 25 2 52.1 / 60.1 94.9 / 105 100 / 110
460-3-60 7.0 52 11 1.3 7.6
None --- --- --- 13.9 20
2NP04501046 10 1 12 28.9 30
2NP04501546 15 1 18 36.4 40
2NH04502046 20 2 24.1 43.9 45
2NP04502546 25 2 30.1 51.4 60
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
BHZ024-060 Heat Pump With/Without Electric Heat (Continued)
Model
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA Model kW Stages Amps