Technical Guide

1055230-YTG-D-0514
Johnson Controls Unitary Products 7
d
ELECTRICAL DATA FOR MULTI-SOURCE POWER SUPPLY: 208/230-1-60
Air
Handlers
Models
Heater
Models
Total
Heater
Amps
@240V
Min. Circuit Ampacity
MOP
1
Min. Wire Size (AWG)
2
208V230V208V230V208V230V
Circuit Circuit Circuit
1st
3
2nd 3rd
1st
3
2nd 3rd
1st
3
2nd 3rd
1st
3
2nd 3rd
1st
3
2nd 3rd
1st
3
2nd 3rd
AHR22B
6HK16501306 52 21.2 37.6 24.4 43.3 25 40 25 45 10 8 10 8
6HK16501506 60 22.8 43.3 27.8 50.0 25 45 30 50 10 8 10 8
AHR24B
6HK16501306 52.0 20.6 37.6 23.4 43.3 25 40 25 45 10 8 10 8
6HK16501506 60.0 23.5 43.3 26.8 50.0 25 45 30 50 10 8 10 8
AHR29C
AHR34C
6HK16501306 52.0 21.3 37.6 24.5 43.3 25 40 25 45 10 8 10 8
6HK16501506 60.0 24.2 43.3 27.9 50.0 25 45 30 50 10 8 10 8
AHR30B
AHR42C
6HK16501306 52.0 22.6 37.6 25.4 43.3 25 40 30 45 10 8 10 8
6HK16501506 60.0 25.5 43.3 28.8 50.0 30 45 30 50 10 8 10 8
AHR36B
AHR48D
6HK16501306 52.0 22.6 37.6 25.4 43.3 25 40 30 45 10 8 10 8
6HK16501506 60.0 25.5 43.3 28.8 50.0 30 45 30 50 10 8 10 8
6HK16501806 72.0 42.8 39.0 48.8 45.0 45 40 50 45 –88–88–
6HK16502006 80.0 47.1 43.3 53.8 50.0 50 45 60 50 –88–68–
AHR60D
6HK16501306 52.0 22.6 37.6 25.4 43.3 25 40 30 45 10 8 10 8
6HK16501506 60.0 25.5 43.3 28.8 50.0 30 45 30 50 10 8 10 8
6HK16501806 72.0 42.8 39.0 48.8 45.0 45 40 50 45 –88–88–
6HK16502006 80.0 47.1 43.3 53.8 50.0 50 45 60 50 –88–68–
6HK16502506 100 47.1 43.3 21.7 53.8 50.0 25.0 50 45 25 60 50 25 6 6 10 6 8 10
1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
2. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
3. 1st Circuit includes the blower motor amps.
ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY - 208/230-3-60
Air Handler Models
Heater
Models
Heater
Amps
@ 240V
Field Wiring
Min. Circuit Ampacity
MOP
1
Min. Wire Size (AWG)
2
208V 230V 208V 230V 208V 230V
AHR18B 6HK06501025 23.1 26.8 30.7 30 35 10 10
AHR24B
6HK06501025 23.1 26.8 30.7 30 35 10 10
6HK06501525 34.6 39.2 45.0 40 45 8 8
AHR30B
AHR42C
6HK06501025 23.1 28.8 32.7 30 35 10 8
6HK06501525 34.6 41.2 47.0 45 50 8 8
AHR36B
AHR48D
6HK06501025 23.1 28.8 32.7 30 35 10 8
6HK06501525 34.6 41.2 47.0 45 50 8 8
6HK06501825 41.6 48.8 55.8 50 60 8 6
6HK16502025
3
46.2 53.8 61.5 60 70 6 6
AHR60D
6HK06501025 23.1 28.8 32.7 30 35 10 8
6HK06501525 34.6 41.2 47.0 45 50 8 8
6HK06501825 41.6 48.8 55.8 50 60 8 6
6HK16502025
3
46.2 53.8 61.5 60 70 6 6
6HK16502525
3
57.7 66.3 75.9 70 80 4 4
1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
2. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
3. The 20kW and 25kW heater models (6HK16502025 and 6HK16502525) come with circuit breakers standard. Single source power MCA and MOP requirements are
given here only for reference if used with field installed single point power modification.