user manual

528150-YTG-G-1210
46 Johnson Controls Unitary Products
115°F 125°F
2125
77 101.7 9.7 38.8 35.0 25.9 - - - 91.0 10.3 34.9 30.1 22.7 - - -
72 92.3 9.4 58.1 49.0 39.9 30.8 - - 82.4 10.0 54.4 45.4 36.5 27.5 - -
67 82.9 9.1 77.4 63.0 53.9 44.8 35.7 - 73.8 9.7 73.8 59.2 50.2 41.3 32.3 -
62 78.3 8.9 78.3 78.3 62.9 53.8 44.7 35.6 71.2 9.5 71.2 71.2 56.5 47.6 38.6 29.7
2550
77 103.6 9.7 49.8 39.2 28.6 - - - 92.7 10.4 48.3 35.8 25.3 - - -
72 94.1 9.4 65.3 54.7 44.1 33.5 - - 83.9 10.1 61.7 51.1 40.5 30.0 - -
67 84.5 9.2 80.8 70.2 59.6 49.0 38.3 - 75.2 9.7 75.2 66.4 55.8 45.2 34.7 -
62 79.7 9.0 79.7 79.7 69.5 58.9 48.3 37.6 72.4 9.6 72.4 72.4 62.9 52.3 41.7 31.2
57 79.2 9.0 79.2 78.8 68.2 57.6 46.9 36.3 72.9 9.6 72.9 72.3 58.4 47.8 37.2 26.6
2975
77 105.6 9.8 60.8 43.4 31.3 - - - 94.3 10.5 61.6 41.6 27.8 - - -
72 95.8 9.5 72.5 60.4 48.2 36.1 - - 85.4 10.2 69.0 56.8 44.6 32.4 - -
67 86.1 9.2 84.3 77.4 65.2 53.1 40.9 - 76.5 9.8 76.5 73.6 61.4 49.2 37.0 -
62 81.2 9.0 81.2 81.2 76.1 63.9 51.8 39.7 73.7 9.6 73.7 73.7 69.2 57.0 44.9 32.7
57 80.7 9.1 80.7 80.5 74.6 62.5 50.3 38.2 74.2 9.7 74.2 73.9 64.3 52.1 39.9 27.7
3400
77 107.5 9.8 71.8 47.6 34.0 - - - 95.9 10.6 74.9 47.3 30.4 - - -
72 97.6 9.6 79.7 66.1 52.4 38.7 - - 86.8 10.2 76.3 62.5 48.7 34.9 - -
67 87.7 9.3 87.7 84.5 70.9 57.2 43.5 - 77.8 9.9 77.8 77.8 67.0 53.2 39.4 -
62 82.7 9.1 82.7 82.7 82.7 69.0 55.3 41.7 75.0 9.7 75.0 75.0 75.0 61.8 48.0 34.2
57 82.1 9.1 82.1 82.1 81.1 67.4 53.7 40.1 75.4 9.8 75.4 75.4 70.3 56.5 42.6 28.8
3825
72 96.2 9.6 85.3 70.4 55.4 40.5 - - 83.7 10.3 81.4 66.4 51.4 36.4 - -
67 86.4 9.3 86.4 84.8 74.9 60.0 45.0 - 74.9 9.9 74.9 74.9 70.8 55.8 40.8 -
62 81.5 9.2 81.5 81.5 81.5 66.5 51.6 36.6 72.3 9.8 72.3 72.3 72.3 57.6 42.6 27.6
57 80.9 9.2 80.9 80.9 80.4 65.5 50.5 35.6 72.8 9.8 72.8 72.8 70.2 55.2 40.2 25.2
4250
72 94.7 9.7 90.9 74.7 58.4 42.2 - - 80.5 10.3 80.5 70.3 54.1 38.0 - -
67 85.1 9.4 85.1 85.1 79.0 62.8 46.5 - 72.1 10.0 72.1 72.1 72.1 58.3 42.2 -
62 80.3 9.2 80.3 80.3 80.3 64.1 47.8 31.6 69.7 9.8 69.7 69.7 69.7 53.5 37.3 21.1
57 79.7 9.2 79.7 79.7 79.7 63.5 47.3 31.0 70.2 9.9 70.2 70.2 70.2 54.0 37.8 21.7
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZH102 (8.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65