Specifications
279550-YIM-E-0610
Johnson Controls Unitary Products 7
Figure 3: Unit Dimensions
A 
B 
VENT AIR OUTLET HOOD 
BLOWER SERVICE ACCESS 
COMPARTMENT PANEL 
GAS SUPPLY
1-1/4" DIAMETER HOLE
(1/2" NPTF CONNECTION)
UNIT CONDENSATE 
CONNECTION 3/4" NPTF 
(TRAP RECOMMENDED)
HIGH VOLTAGE 
CONN. 1-3/8" DIA. 
KNOCKOUT 
3-3/4 
2-1/2 
GAS SUPPLY
1-1/4" DIA. KNOCKOUT
(1/2" NPTF CONNECTION)
LOW VOLTAGE 
CONN.1-3/8" DIA. 
KNOCKOUT x 7/8" HOLE 
(OVERALL) 
(OVERALL) 
CONDENSER COIL 
2-3/8 
REFRIGERANT 
CONNECTIONS 
COMBUSTION AIR 
INLET LOUVERS 
FRONT 
GAS/ELECTRIC CONTROL 
SERVICE ACCESS 
COMPARTMENT PANEL 
1-1/2 
2-5/8 
3-1/3 
12-3/4 
11 
5-3/8 
49-1/8 
47-1/4 
Table 4: Unit Dimensions
Unit Size
Dimensions
“A” “B”
024 33-1/2 18-1/4
036, 048 41-1/2 23-1/8
Table 5: Unit Clearances
1
2
1. A 1" clearance must be provided between any combustible material and the supply air duct work.
2. The products of combustion must not be allowed to accumulate within a confined space and recirculate.
Direction
Distance
(in.)
Direction
Distance
(in.)
Top
3
3. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air 
discharge outlet.
36 Right 12
Front 36 Left 24
Rear 0 Bottom
4
4. Units may be installed on combustable floors made from wood or class A, B or C roof covering 
materials.
0