Specifications
268721-YIM-B-0807
Unitary Products Group 11
Compressors
The scroll compressor used in this product is specifically
designed to operate with R-410A Refrigerant and cannot be
interchanged.
The compressor also uses a polyolester (POE oil), Mobil 3MA
POE. This oil is extremely hydroscopic, meaning it absorbs
water readily. POE oil can absorb 15 times as much water as
other oils designed for HCFC and CFC refrigerants. Take all
necessary precautions to avoid exposure of the oil to the
atmosphere.
POE (polyolester) compressor lubricants are known to cause
long term damage to some synthetic roofing materials.
Procedures which risk oil leakage include, but are not limited to,
compressor replacement, repairing refrigerant leaks, replacing
refrigerant components such as filter drier, pressure switch,
metering device or coil.
Units are shipped with compressor mountings which are
factory-adjusted and ready for operation.
Phasing
Three-phase, scroll compressors operate in only one direction.
If the scroll is drawing low amperage, has similar suction and
discharge pressures, or is producing a high noise level, the
scroll is misphased. Change the incoming line connection
phasing to obtain the proper rotation.
CONDENSER FAN DATA
Fan diameter (Inch) 22 22 22 22 22 22
Type Prop Prop Prop Prop Prop Prop
Drive type Direct Direct Direct Direct Direct Direct
No. speeds 1 1 1 1 1 1
Number of motors 1 1 1 1 1 1
Motor HP each 1/4 1/4 1/4 1/4 1/4 1/2
RPM 850 850 850 850 850 1100
Nominal total CFM 1800 1800 2400 2400 3000 3000
DIRECT DRIVE EVAP FAN DATA
Quantity 1 1 1 1 1 1
Fan Size (Inch) 10 x 8 10 x 8 11 x 10 11 x 10 11 x 10 11 x 10
Type Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal
No. speeds 5 5 5 5 5 5
Motor HP each 1/2 1/2 3/4 3/4 3/4 1
RPM Variable Variable Variable Variable Variable Variable
Frame size 48 48 48 48 48 48
FILTERS
Quantity - Size 2 - 22 x 14 x 1 2 - 22 x 14 x 1 2 - 22 x 14 x 1 2 - 22 x 14 x 1 2 - 22 x 14 x 1 2 - 22 x 14 x 1
Table 6: Physical Data (Continued)
Component
Models
BHZ024 BHZ030 BHZ036 BHZ042 BHZ048 BHZ060
Nominal Tonnage 2.0 2.5 3.0 3.5 4.0 5.0
This system uses R-410A Refrigerant which operates at
higher pressures than R-22. No other refrigerant may be
used in this system.
Do not leave the system open to the atmosphere. Unit
damage could occur due to moisture being absorbed by
the POE oil in the system. This type of oil is highly
susceptible to moisture absorption
Exposure, even if immediately cleaned up, may cause
embrittlement (leading to cracking) to occur in one year
or more. When performing any service that may risk
exposure of compressor oil to the roof, take precautions
to protect roofing.
Do not loosen compressor mounting bolts.
Scroll compressors require proper rotation to operate
properly. Failure to check and correct rotation may result
in property damage.