Technical data
11 DE-COMMISSIONING,
DISMANTLING AND DISPOSAL
Never release refrigerant to the
atmosphere when emptying the
refrigerating circuits. Suitable retrieval
equipment must be used. If reclaimed
refrigerant cannot be re-used. It must
be returned to the manufacturer.
Never discard used compressor oil, as
it contains refrigerant in solution.
Return used oil to the oil manufacturer.
Unless otherwise indicated, the operations
described below can be performed by any properly
trained maintenance technician.
11.1 General
Isolate all sources of electrical supply to the unit
including any control system supplies switched by
the unit. Ensure that all points of isolation are
secured in the 'OFF' position. The supply cables
may then be disconnected and removed. For
connection points refer to Section 4.
Remove all refrigerant from each system of the unit
into a suitable container using a refrigerant reclaim
or recovery unit. This refrigerant may then be re-
used, if appropriate, or returned to the
manufacturer for disposal. Under NO
circumstances should refrigerant be vented to
atmosphere. Drain the refrigerant oil from each
system into a suitable container and dispose of
according to local laws and regulations governing
the disposal of oily wastes. Any spilt oil should be
mopped up and similarly disposed of.
Isolate the unit heat exchanger(s) from all external
water systems and drain the heat exchanger
section(s) of the system. If no isolation valves are
installed it may be necessary to drain the complete
system(s).
If glycol or similar solutions have been
used in the water system(s), or
chemical additives are contained, the
solution MUST be disposed of in a
suitable and safe manner. Under NO
circumstances should any system
containing glycol or similar solutions
be drained directly into domestic
waste or natural water systems.
After draining, the water pipework can be
disconnected and removed.
Packaged units can generally be removed in one
piece after disconnection as above. Any fixing
down bolts should be removed and then the unit
should be lifted from position using the points
provided and equipment of adequate lifting
capacity.
Reference should be made to Section 4 for unit
installation instructions, Section 9 for unit weights
and Section 3 for handling.
Units which cannot be removed in one piece after
disconnection as above, must be dismantled in
position. Special care should be taken regarding
the weight and the handling of each component.
Where possible units should be dismantled in the
reverse order of installation.
Residual refrigerant oil and glycol or
similar solutions may remain in some
parts of the system. These should be
mopped up and disposed of as
described above.
It is important to ensure that whilst components are
being removed the remaining parts are supported
in a safe manner.
Only use lifting equipment of adequate
capacity.
After removal from position the unit parts may be
disposed of according to local laws and regulations
035B40022-000 11-1










