Technical data
9.5 Unit Electrical Data
9.6 Compressor Electrical Data
9-6 035B40022-000
YCWM/YCRM
Model
60
75 90 120 150
Current
Nom. Cond.
30 35 45 64 76
Input (A)
Max. Cond.
34 43 52 73 88
Power
Nom. Cond.
16 19 23 33 41
Input (KW)
Max. Cond.
20 23 29 41 51
Nominal conditions at 7°C chilled water outlet temperature, 35°C condenser outlet temperature (YCWM)
Maximum conditions at 12°C chilled water outlet temperature, 50°C condenser outlet temperature (YCWM)
Nominal conditions at 7°C chilled water outlet temperature, 40°C condensing temperature (YCRM)
Maximum conditions at 12°C chilled water outlet temperature, 55°C condensing temperature (YCRM)
YCWM/YCRM
Model
170
200 240 280
Current
Nom. Cond. 92 104 128 152
Input (A)
Max. Cond. 108 124 152 184
Max. start.
206 243 304 353
Power
Nom. Cond. 49 58 66 81
Input (KW)
Max. Cond. 63 75 85 105
Nominal conditions at 7°C chilled water outlet temperature, 35°C condenser outlet temperature (YCWM)
Maximum conditions at 12°C chilled water outlet temperature, 50°C condenser outlet temperature (YCWM)
Nominal conditions at 7°C chilled water outlet temperature, 40°C condensing temperature (YCRM)
Maximum conditions at 12°C chilled water outlet temperature, 55°C condensing temperature (YCRM)
Model
Power
Power Current Max. DOL Max.
YCWM/
Input at
Input at at Nom Cond. Current Starting Fuse
YCRM
System
Compressor Voltage Nom. Cond. Max. Cond. per Comp. per Comp. Current (A) Size
(V)
per Comp. (kW) per Comp. (kW) (A) (A) LRA (A)
60
1+2
H7BG1244008 1015179320
75
1+2
H75G144 400 9 12 18 22 110 25
90
1+2
H7NG184 400 12 14 23 26 125 25
120
1+2
H7NG244 400 16 20 32 37 190 40
150
1+2
H7NG294 400 20 25 38 44 215 50
Nominal conditions at 7°C chilled water outlet temperature, 35°C condenser outlet temperature (YCWM)
Maximum conditions at 12°C chilled water outlet temperature, 50°C condenser outlet temperature (YCWM)
Nominal conditions at 7°C chilled water outlet temperature, 40°C condensing temperature (YCRM)
Maximum conditions at 12°C chilled water outlet temperature, 55°C condensing temperature (YCRM)
Power
Power Current Max. DOL Max.
Model
Input at
Input at at Nom Cond. Current Starting Fuse
YCWM
System
Compressor Voltage Nom. Cond. Max. Cond. per Comp. per Comp. Current (A) Size
YCRM
(V)
per Comp. (kW) per Comp. (kW) (A) (A) LRA (A)
170
1+2+3+4
H2NG184 400 12 15 23 27 125 120
200
1+2+3+4
H2NG204 400 14 18 26 31 150 160
240
1+2+3+4
H2NG244 400 17 21 32 38 190 200
280
1+2+3+4
H2NG294 400 21 27 38 46 215 250
Nominal conditions at 7°C chilled water outlet temperature, 35°C condenser outlet temperature (YCWM)
Maximum conditions at 12°C chilled water outlet temperature, 50°C condenser outlet temperature (YCWM)
Nominal conditions at 7°C chilled water outlet temperature, 40°C condensing temperature (YCRM)
Maximum conditions at 12°C chilled water outlet temperature, 55°C condensing temperature (YCRM)