Technical information

18
9 - Performances B4IH
9.1.- Cooling capacities B4IH - 360
9.2.- Cooling capacities B4IH - 480
Data in compliance with EUROVENT conditions.
Return air
Air temperature in outdoor coil (DB)
27°C 35°C 46°C
Total
power
kW
Sensible power kW
Total
power
kW
Sensible power kW
Total
power
kW
Sensible power kW
m
3
/h
DB
°C
Intake temp. DB Intake temp. DB Intake temp. DB
30 27 24 22 30 27 24 22 30 27 24 22
Minimum
flow
19.000
23 123.3 79.3 61.0 42.6 - 117.7 77.1 58.9 40.5 - 105.4 73.6 55.2 37.0 -
19 111.7 106.5 88.2 69.8 57.6 105.4 104.0 85.7 67.4 55.1 94.9 94.9 81.2 63.6 51.4
17 105.4 105.4 101.5 83.1 70.9 97.0 97.0 95.5 77.2 65.0 86.4 86.4 86.4 75.2 63.0
15 94.9 94.9 94.9 93.7 81.5 90.6 90.6 90.6 87.4 75.2 81.1 81.1 81.1 81.1 75.4
Nominal
flow
21.000
23 125.9 83.9 63.7 43.6 - 119.4 81.7 61.6 41.4 - 107.6 78.1 58.0 37.9 -
19 114.0 113.6 93.5 73.3 60.0 107.6 107.6 91.0 70.8 57.4 96.8 96.8 87.2 67.1 53.6
17 107.6 107.6 107.6 87.9 74.4 99.0 99.0 99.0 81.6 68.2 88.2 88.2 88.2 80.0 66.5
15 96.8 96.8 96.8 96.8 86.2 92.5 92.5 92.5 92.5 79.5 82.9 82.9 82.9 82.9 80.2
Maximum
flow
23.000
23 127.7 88.3 66.3 44.3 - 121.2 86.1 64.2 42.2 - 109.2 82.5 60.6 38.7 -
19 115.7 115.7 98.5 76.6 62.0 109.2 109.2 96.0 74.1 59.5 98.3 98.3 92.2 70.3 56.7
17 109.2 109.2 109.2 92.3 77.8 100.5 100.5 100.5 85.8 71.2 89.5 89.5 89.5 84.4 69.7
15 98.3 98.3 98.3 98.3 90.8 93.9 93.9 93.9 93.9 83.5 84.1 84.1 84.1 84.1 84.1
Return air
Air temperature in outdoor coil (DB)
27°C 35°C 46°C
Total
power
kW
Sensible power kW
Total
power
kW
Sensible power kW
Total
power
kW
Sensible power kW
m
3
/h
DB
°C
Intake temp. DB Intake temp. DB Intake temp. DB
30 27 24 22 30 27 24 22 30 27 24 22
Minimum
flow
22.000
23 159.8 97.9 76.6 55.2 - 151.6 95.1 73.7 52.3 - 136.6 90.4 69.0 47.6 -
19 144.8 130.0 108.5 87.2 73.0 136.6 126.7 105.3 84.0 69.7 123.0 121.7 100.3 78.9 64.7
17 136.6 136.6 124.1 102.7 88.5 125.6 125.6 116.7 95.3 81.1 112.0 112.0 112.0 92.3 78.1
15 123.0 123.0 123.0 114.7 100.5 117.4 117.4 117.4 107.0 92.8 105.2 105.2 105.2 105.2 92.6
Nominal
flow
25.000
23 163.8 104.8 80.7 56.6 - 155.4 102.0 77.8 53.7 - 140.0 97.2 73.1 49.0 -
19 148.4 140.6 116.5 92.4 76.3 140.0 137.3 113.2 89.1 73.0 126.0 126.0 108.2 84.1 68.0
17 140.0 140.0 133.9 109.8 93.7 128.8 128.8 126.0 101.8 85.8 114.8 114.8 114.8 99.3 83.2
15 126.0 126.0 126.0 123.7 107.6 120.4 120.4 120.4 115.3 99.2 107.8 107.8 107.8 107.8 99.6
Maximum
flow
28.000
23 166.7 111.3 84.5 57.8 - 158.2 108.5 81.7 54.9 - 142.5 103.7 77.0 50.2 -
19 151.0 150.8 124.0 97.3 79.4 142.5 142.5 120.7 94.0 76.1 128.2 128.2 115.7 89.0 71.1
17 142.5 142.5 142.5 116.6 98.7 131.1 131.1 131.1 108.3 90.3 116.8 116.8 116.8 106.0 88.2
15 128.2 128.2 128.2 128.2 114.4 122.5 122.5 122.5 122.5 105.3 109.7 109.7 109.7 109.7 106.4