<-- SPLIT SYSTEM YORK ®
<-- Index Page General description 5 - Nomenclature 5 Technical specifications 5 - Mechanical specifications of outdoor units AHO-F - Mechanical specifications of indoor unit CHI-800 - Table of variations - Physical data - Rated performance data - Testing conditions - Correction factors - Cooling capacities sensitives - CHI-800 fan performance 5 5 6 7 8 8 8 8 - 10 10 Installation instructions 11 - 11 11 11 11 11 11 12 12 12 12 2 General comments Protection of the environment Warning signals Tr
<-- General description The units in the SOC range are the outdoor units of a splittype air conditioner; they are fitted with a vertical discharge axial fan and have been designed for installation outdoors. Units SOC-076 to 180 are compatible with indoor units SIC-076 to 60. In winter they can provide heat if the indoor unit SIC is fitted with an electric heater or a hot water coil (optional accessories). The outdoor unit SOC-240 is compatible with the SIC-240.
<-Table of variations SOC-076 220/240.3.50 380/415.3.50 SIC-076 220/240.3.50 380/415.3.50 SOC-090 220/240.2.50 380/415.3.50 SIC-090/120 220/240.3.50 380/415.3.50 SOC-120 220/240.3.50 380/415.3.50 SIC-150 380/415.3.50 SOC-150 380/415.3.50 SOC-180 380/415.3.50 SOC-240 380/415.3.50 4 SIC-180 380/415.3.50 SIC-240 380/415.3.
<-- Physical data Outdoor units Model SOC 076 SOC 090 SOC 120 1 1 1 Reciprocating Scroll 8.4 10.2 Quantity Type SOC 150 SOC 180 SOC 240 2 2 2 Reciprocating Reciprocating Scroll Reciprocating 12.2 2 x 8.4 2 x 10.2 2 x 12.2 Compressor Nominal power kW Power supply V.ph.Hz Power rating W Number of fans Outdoor fan Power supply 380/415.3.50 216 216 216 216 216 216 2 2 3 4 6 6 V.ph.Hz. Propeller width Quantity Indoor coil 220/240.3.50 or 380/415.3.
<-Rated performance data Summer Outoor unit Indoor unit Cooling capacity W Available pressure indoor blower Pa Consumption W SOC-076 SIC-076 19 700 9 120 62 SOC-090 SIC-090/120 27 600 11 200 62 SOC-120 SIC-090/12 35 800 14 000 62 SOC-150 SIC-150 40 200 17 400 80 SOC-180 SIC-180 55 200 22 400 80 SOC-240 SIC-240 71 600 28 000 80 Note: SIC units have their own information available. Testing conditions Summer Length of interconnection line Voltage V.
<-- Cooling capacities sensitives Sensitive capacity (W/h) Model Outdoor air dry temperature °C (DB) 25 SOC-090/ SIC-090/120 35 45 25 SOC-120/ SIC-090/120 35 45 25 SOC-150/ SIC-150 35 45 Air intake humid temperature °C (WB) Total capacity Compressor absorbed power Temperature air going to indoor unit °C (DB) 22 24 27 29 W/h W/h W/h W/h W/h kW 22 34 800 10 426 15 008 21 879 26 466 6.24 19.5 31 320 16 167 20 748 27 619 31 320 6.
<-Cooling capacities sensitives Sensitive capacity (W/h) Model Outdoor air dry temperature °C (DB) Air intake humid temperature °C (WB) 25 SOC-180/ SIC-180 35 45 25 SOC-240/ SIC-240 35 45 Total capacity Compressor absorbed power Temperature air going to indoor unit °C (TS) 22 24 27 29 W/h W/h W/h W/h W/h kW 22 64 800 19 662 27 333 38 841 46 524 12.60 19.5 58 320 29 237 36 909 48 417 56 102 13.20 17 54 000 39 432 47 104 54 000 54 000 13.
<-- Installation instructions General comments The SOC series units are outdoor units of a split air conditioner which are equipped with an axial and vertical discharge fan, and are to be installed directly outdoors. For operation, these units must be connected, electrically and with regard to the refrigerant, to the corresponding indoor unit. Attention: Fan in operation. Protection of the environment Packing The packing material is recyclable.
<-Air ducts (indoor unit) 1.- Connect the ducts, isolating from the unit by means of a flexible hose, preferably of a non-combustible material, so as to avoid transmitting the vibration of the unit itself. If the ducts are made of flexible material they do not transmit vibrations. 2.- It is advisable to place a damper at each discharge duct derivation so as to be able to carry out a correct balance of the system. 3.- Make sure there is easy access for cleaning and changing the air filters.
<-- contamination and obstructions. 7- For copper-copper joints do not use strippers. Wiring installation Diameter of the interconnecting tubing Diameter gas line (wide tubing) Model Diameter liquid line (narrow tubing) SOC-076 & 150 1/2" (12.7 mm) 11/8 " (28.5 mm) SOC-090, 120, 180 & 240 The air conditioners are supplied with a control box to which the power supply is to be connected through a main switch with fuses, or an automatic switch.
<-- Indoor units Power supply V.ph.Hz. Consumption A Fan Model Power supply cable section Automatic switch mm2 A Fan Start Nominal 220/240.3.50 14 5,2 4 x 2.5 - 380/415.3.50 7 2 4 x 2.5 - 220/240.3.50 23 5.5 4 x 2.5 - 380/415.3.50 10 3.2 4 x 2.5 - 220/240.3.50 23 5.7 4 x 2.5 - 380/415.3.50 10 3.3 4 x 2.5 - SIC-150 380/415.3.50 10 3.5 4 x 2.5 - SIC-180 380/415.3.50 27 7.1 4 x 2.5 15 SIC-240 380/415.3.50 30 6.4 4 x 2.
<-- Dial set to the desired temperature index. Instructions for use General information The start up and automatic temperature setting is carried out by means of the ambient thermostat, at 24 volts, specially designed for these units. Depending upon the model of your air conditioner, same will be controlled by the corresponding thermostat.
<-- is set to "AUTO" and lever B to "OFF". T-22 thermostat Maintenance Keep the battery filters in good condition, checking them at least once a month. If the filters are dirty, air flow and equipment performance are reduced. Cleaning the outdoor unit CAUTION Dirt should not be allowed to accumulate in the outdoor battery. It should be cleaned as frequently as needed, Clean the casing and the grill of the indoor unit either with a vacuum cleaner or a rag soaked in a soft liquid detergent.
General dimensions mm SIC-240 EMPTY SPACE 600 827 203 8 25 142 .5 985 633 758 404 473 225 473 381 93 .5 363 2323 80 142 40 EMPTY ESPACE 600 "A" DETAIL EMPTY SPACE 600 DRAINAGE R 3/4" "A" DETAIL 236 140 104 5 37 163 37 100 572 LIQUID CONNECTION 5/8" GAS CONNECTION 11/8" 40 28 SOC-076, 090 & 120 945 <-- EMPTY SPACE 600 GAS TUBING CONNECTION ACCESS 11/8" D. 13.
<-General dimensions mm SOC-150, 180 & 240 1495 EMPTY SPACE 600 CUTOUT PUSH-BUTTONS GAS TUBING CONNECTION ACCESS 11/8" LIQUID TUBING CONNECTION ACCESS (C) EMPTY SPACE 600 EMPTY SPACE 1000 D. 16.5 DRAINAGE CONNECTION 20 425 7 B 150 A 175 Models A B C SOC-150 1 690 1 090 1/2" SOC-180 1 975 1 375 5/8" SOC-240 2 150 1 550 5/8" All data subject to change without notice.
<-- DEFINITIVE SHUTDOWN, DISASSEMBLY & DESTRUCTION This product includes a refrigerant gas under pr essur e, moving parts and electric components which may be dangerous and cause injury ! All servicing must be done by qualified personnel, wearing protective clothing, in compliance with applicable safety r ules. Read the Manual 1. 2. 3. 4.