9.2.3 Limit Switch Threshold
The Limit switch thresholds apply to the Discrete Input (DI) block setpoints.
Threshold Low
The threshold for the low limit switch that communicated by the DI block.
Threshold High
The threshold for the high limit switch that communicated by the DI block.
9.2.4 Fault Control
Error Band
The position deviation limit to start deviation timer of Time 1 and Time 2.
Set this value to a value that is exceeded only in abnormal performance.
Time 1
The position deviation time limit to show the block alarm. A negative value turns off this
function. Set this value greater than the stroking time.
Time 2
The position deviation time limit to trigger the failsafe action. Enter “-1” to disable this
function. A negative value turns off this function. Use of the Time 2 failsafe may result in
unwanted process shutdowns.
WARNING
Use the Time 2 failsafe only for a critical process that must be forced into its failsafe position
if the valve is unable to respond to its position setpoint after a reasonable time delay. Do
not set the error band to a value that is too small. If Time 2 is used, it must be longer than
the valve stroking time. A Time 2 value that is too small will result in nuisance failsafe
behavior.
9.2.5 Servo Alarms (I/P Module Operating Point Fault Control)
This function is applicable only to the device revision 4 or higher (or the device revision 2 or
higher when the software download functions are available).
Servo Warning High
If the operating point of the I/P module is more than this value, the timer that measures the
time after the I/P module operating point error starts.
Servo Warning Low
If the operating point of the I/P module is less than this value, the timer that measures the
time after the I/P module operating point error starts. Input a value that is the same as or
less than that for Servo Warning High.