User Manual

<7. Standard Specications>
7-1
IM 21B04C01-01E
7. Standard Specications
Standard Specications
Applicable Control Valve:
Linear or Rotary Motion Control Valve
(Diaphragm Actuator and Cylinder)
Functions:
Function Blocks:
AO: One Analog Output
DI: Two Discrete Inputs
OS: One Splitter Block
IS: One Input Selector
AR: One Arithmetic
PID: One or Two PID Control Functions
(Optional)
NOTE
IS, AR and PID (2 blocks) function blocks are
applicable for only software download function
(/EE).
Link Master Function
Pressure Sensor (Optional)
Flow Characterization Feature:
Linear
Equal Percentage (50 : 1)
Equal Percentage (30 : 1)
Quick Opening
Camex Percentage
Customer Characterization (10 segments)
Auto Tuning Function
Valve Position Detecting Function
Contiuous Diagnostics Function:
Total Travel
Number of Cycles
Time Open/Time Close/Time Near Close
Housing Materials:
Case: Aluminum die-cast
Paint: Polyurethane resin-baked nish
Color: Deep-sea moss-green
(Munsell 0.6GY3.l/2.0 or equivalent)
Communication:
Digital: F
OUNDATION eldbus
Supply Voltage:
9 to 32V DC for general use and ameproof
type
9 to 24V DC for intrinsically safe type Entity
model
9 to 17.5V DC for intrinsically safe type FISCO
model
Conditions of Communication Line
Supply Voltage: 9 to 32V DC
Current Draw:
Steady state: 17 mA max.
Software download state: 41 mA max.
Output Signals and Pressure Gauge Scale:
No gauge in standard. Pressure gauge can be
selected as option. The supply pressure unit on
the name plate for non-gauge model is Pa.
Diaphragm, Single acting Cylinder
Calibration
unit
Supply Air
Pressure
Pressure Gauge Scale
Supply Air Output Signal
Pa 140 to 400 kPa 400 kPa 400 kPa
kgf/cm
2
1.4 to 4 kgf/cm
2
4 kgf/cm
2
4 kgf/cm
2
bar 1.4 to 4 bar 4 bar 4 bar
psi 20 to 60 psi 60 psi 60 psi
Double acting Cylinder
Calibration
unit
Supply Air
Pressure
Pressure Gauge Scale
Supply Air Output Signal
Pa 200 to 700 kPa 1 MPa 1 MPa
kgf/cm
2
2 to 7 kgf/cm
2
10 kgf/cm
2
10 kgf/cm
2
bar 2 to 7 bar 10 bar 10 bar
psi 30 to 105 psi 150 psi 150 psi
Pressure Gauge Case:
Stainless steel JIS SUS 304
Normal Operating Conditions:
Air Supply pressure:
Single Acting Actuator:
20 to 60 psi (140 to 400 kPa)
Double Acting Actuator:
30 to 100 psi (200 to 700 kPa)
Vibration Limit: 4 mm at 5 to 15 Hz;
2G at 15 to 2000 Hz
Shock limit: 10G
Manual Operation:
Available using Auto/Manual (A/M) transfer
switch
Zero Adjustment Range:
–15 to 85% of span