User Manual

<1. Notes on Handling>
1-5
IM 21B04C01-01E
SAFE AREA HAZARDOUS AREA
F0103.ai
Terminator
(FISCO Model)
Ex i
Field Instruments
(Passive)
Supply Unit
(FISCO Model)
Terminator
Data
U
U
I
Note 5. Maintenance and Repair
The instrument modication or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation is prohibited and will void Factory
Mutual Intrinsically Safe and Non-incendive
Approval.
l Installation Diagram (Nonincendive,
Division 2 Installation)
F0104.ai
Terminator
Valve Positioner
Terminator
+
Transmitter
+
Transmitter
+
Hazardous Location
Non-hazardous Location
FM Approved Associated
Nonincendive Field Wiring Apparatus
Vt or Voc
It or Isc
Ca
La
(Nonincendive)
Power Supply
*1: Dust-tight conduit seal must be used when
installed in Class II and Class III environments.
*2: Installation should be in accordance with the
National Electrical Code® (ANSI/NFPA 70)
Sections 504 and 505.
*3: The conguration of Associated Nonincendive
Field Wiring Apparatus must be FM Approved.
*4: Associated Nonincendive Field Wiring
Apparatus manufacturers installation
drawing must be followed when installing this
equipment.
*5: No revision to drawing without prior FM
Approvals.
*6: Terminator and supply unit must be FM
Approved.
*7: If use ordinary wirings, the general purpose
equipment must have nonincendive eld wiring
terminal approved by FM Approvals.
*8: The nonincendive eld wiring circuit concept
allows interconection of nonincendiveeld
wiring apparatus with associated nonincendive
eld wiring apparatus, using any of the wiring
methods permitted for unclassied locations.
*9: Installation requirements;
Vmax Voc or Vt
Imax = see note 10.
Ca Ci + Ccable
La Li + Lcable
*10: For this current controlled circuit, the parameter
(Imax) is not required and need not be aligned
with parameter (Isc or It) of the barrier or
associated nonincendive eld wiring apparatus.
Electrical Data:
Maximum Input Voltage Vmax: 32 V
Maximum Internal Capacitance Ci: 1.76 nF
Maximum Internal Inductance Li: 0 µH
B) FM Explosionproof Type
Caution for FM explosionproof type.
Note 1. Model YVP110 Valve Positioner with
optional code /FF1 are applicable for use in
hazardous locations.
Applicable standard: FM3600, FM3615,
FM3810, ANSI/NEMA250
Explosionproof for Class I, Division 1,
Groups A, B, C and D
Dust-ignitionproof for Class II/III, Division 1,
Groups E, F and G
Enclosure Rating: NEMA 4X
Temperature Class: T6
Ambient Temperature: –40 to 80°C