User Manual

<Appendix 3. DD Methods and DD Menu>
A-27
IM 21B04C01-01E
5) Travel Calibration
This method guides you through each step to
carry out travel calibration. See the respective
descriptions in Section 5.3, “Carrying out Auto
Tuning.
Travel calibration procedure
AO/Transducer block mode check
Execute travel calibration
0% calibration:
Adjustment of FINAL_VALUE (by moving
the valve position to the desired 0%
position)
Execute 0% calibration:
TRAVEL_CALIB_EXEC
Span calibration:
Adjustment of FINAL_VALUE (by moving
the valve position to the desired 100%
position)
Execute span calibration:
TRAVEL_CALIB_EXEC
50% calibration:
Adjustment of FINAL_VALUE (by moving
the valve position to the desired 50%
position)
Execute 50% calibration:
TRAVEL_CALIB_EXEC
Exit
6) Operational Parameter Conguration
This method guides you through the setting of
individual operational parameters excluding the
selection of position-to-ow rate characteristic type.
Operational parameter conguration procedure
AO/Transducer block mode check
Operational parameter conguration
Position Limit setting:
FINAL_VALUE_CUTOFF_LO
FINAL_VALUE_CUTOFF_HI
FINAL_VALUE_RANGE
Limit Switch setting:
LIM_SW_LO_LIM
LIM_SW_HI_LIM
Fault Control:
DEVIATION_LIM
DEVIATION_TIME_TH(1)
DEVIATION_TIME_TH(2)
Others:
NEAR_CLOSE_THRESHOLD
Exit
7) Release Fail Safe
This is a method for releasing the device latched by
the fail-safe actions, restoring it to the normal state.
Procedure of releasing fail safe
Check whether the device is in the latched
state.
Write “Clear-latched” to parameter RELEASE_
FAIL_SAFE if the device is in the latched state,
to release it from the latched state.
8) Instant Trouble Shooting
This is a help utility which provides troubleshooting
instructions such as indicating the points and
parameters to be checked for troubleshooting.
This method does not contain a utility to change
parameter settings. For troubleshooting of device
statuses, see Chapter 18, “Troubleshooting.
Instant troubleshooting procedure
Commanded to check DEVICE_STATUS in the
resource block
Check XD_ERROR and the remedy will be
displayed if an error has been detected
Check RELEASE_FAIL_SAFE
Commanded to check the mechanical linkage,
piping, and installation conditions
Commanded to check the correct operation of
the device hardware
9) Self Check Execution
The self-check measures the valve’s characteristics
in the same fashion as in auto tuning, and makes
no changes to parameter settings.
Self Check Execution procedure
AO/TB block mode check
Self check execution: AUTO_TUNE_EXEC
10) Signature Execution
This method guides you through each step to
perform signature measurement (see Chapter
17, “Diagnostics”). Signature measurement
entails off-line diagnostics functions to measure
characteristics of the valve and positioner.
Comparing the current signature data with the
previously measured data gives clues to identify
the deterioration status and a possible need of
maintenance.