<Appendix 1. Function Block Parameters>
A-18
IM 21B04C01-01E
A1.9 IO_OPTS - Availability of Options for Each Block
Bit Contents DI AO
0
Invert
×
1
SP-PV Track in Man
×
2
Reserved
3
SP-PV Track in LO
×
4
SP Track retained target
×
5
Increase to close
×
6
Fault State to value
×
7
Use Fault State value on restart
×
8
Target to Man if Fault State activated
×
9
Use PV for BKCAL_OUT
×
10
Low cutoff
11
Reserved (SIS-Latch Fstate)
12
Units Conversion
A1.10 STATUS_OPTS - Availability of Options for Each Block
Bit Contents DI AO OS PID IS
0 IFS if BAD IN ×
1 IFS if BAD CAS_IN × ×
2 Use Uncertain as Good × ×
3 Propagate Fault Forward ×
4 Propagate Fault Backward × ×
5 Target to Manual if BAD IN ×
6 Uncertain if Limited
7 BAD if Limited
8 Uncertain if Man mode × ×
9 Target to next permitted mode if Bad CAS_IN ×
A1.11 CONTROL_OPTS - Availability of Options for Each Block
Bit Contents PID
0 Bypass Enable ×
1 SP-PV Track in Man ×
2 SP-PV Track in ROut ×
3 SP-PV Track in LO or IMan ×
4 SP Track retained target ×
5 Direct Acting ×
6 Reserved
7 Track Enable ×
8 Track in Manual ×
9 Use PV for BKCAL_OUT ×
10 Act on IR
11 Use BKCAL_OUT with IN_1
12 Obey SP limits if Cas or RCas ×
13 No OUT limits in Manual ×
14 Reserved
15 Reserved