User Manual

<Appendix 1. Function Block Parameters>
A-3
IM 21B04C01-01E
Relative
Index
Index Parameter Name
Default
(factory setting)
Write Description
39 1039 WRITE_PRI 0 . Denes the priority level of WRITE_ALM as well
as allows for notication to be disabled and makes
acknowledgment unnecessary for WRITE_ALM
40 1040 WRITE_ALM Alarm generated when WRITE_LOCK is set to
unlocked
41 1041 ITK_VER Version number of the inter-operability test kit
42 1042 SOFT_REV Revision number of software
43 1043 SOFT_DSC Revision number of software for development
purpose.
44 1044 SIM_ENABLE_MSG Null Used to determine whether to enable the
simulation function to run. To enable, set
“REMOTE LOOP TEST SWITCH”.
45 1045 DEVICE_STATUS_1 0 Shows device statuses - mainly link object setting
statuses.
46 1046 DEVICE_STATUS_2 0 Shows device statuses - mainly individual for each
block status.
47 1047 DEVICE_STATUS_3 0 Shows device statuses - mainly the contents of
XD_ERROR in each block.
48 1048 DEVICE_STATUS_4 0 Not used in the YVP110.
49 1049 DEVICE_STATUS_5 0 Not used in the YVP110.
50 1050 DEVICE_STATUS_6 0 Not used in the YVP110.
51 1051 DEVICE_STATUS_7 0 Not used in the YVP110.
52 1052 DEVICE_STATUS_8 0 Not used in the YVP110.
*1: FF-891 “Foundation
TM
Specication Function Block Application Process Part 2”
A1.2 Parameters of Transducer Block
Parameters marked with (*1) are automatically set and changed by autotuning. Parameters marked with (*2)
are automatically set and changed by Travel calibration.
Relative
Index
Index Parameter Name
Default
(factory setting)
Write Description [Setting range]
0 2000 Block Header Block tag
= O/S
Information about this block, including the block
tag, DD revision, execution time
1 2001 ST_REV 0 Incremented when a change is made to the
parameter settings for the transducer block to
indicate the revision level of the settings, and
used to see whether or not there is a change in
parameter settings.
2 2002 TAG_DESC Spaces Universal parameter storing the description of the
tag
3 2003 STRATEGY 1 Universal parameter used by an upper-level
system to classify the function blocks.
4 2004 ALERT_KEY 1 Universal parameter used as a key to identify
the point from which an alert is issued; normally
used by an upper-level system to select alerts
to provide to a particular operator who covers a
specic area of the plant.
5 2005 MODE_BLK O/S Universal parameter that indicates the block
operation conditions and is composed of the
actual mode, target mode, permitted modes, and
normal mode.
6 2006 BLOCK_ERR Indicates the error statuses related to the block
itself.
7 2007 UPDATE_EVT Shows the contents of an update event upon
occurrence.
8 2008 BLOCK_ALM Universal parameter indicating the hardware and
software error statuses related to the block itself