Manual
    <7.GeneralSpecications>
7-2
IM 01C50B01-01E
Effectofsupplyvoltageuctuation:
±0.005%/V
Insulation:
Input/output insulated at 500 V DC
Mounting:
Mounted on 2B pipes and wall
Degrees of Protection:
IP66/IP67, NEMA 4X
Electrical connection:
Refer to “Model and Specication Codes”.
Case and cover:
Aluminum alloy casting
Painting:
Polyurethane resin baked nish
Deep sea moss green (equivalent of Munsell 
0.6GY3.1/2.0)
Integral indicator (option):
LCD digital indicator (5-digit display)
Output bar graph; 0 to 100% display
Damping constant:
0 to 99 seconds (integer range that can be set)
Sensor burnout (Output Signal Code D&E) :
High (110%, 21.6 mA DC) or Low (–2.5%, 3.6 
mA DC)
Weight:
1.2 kg; without built-in indicator (without 
mounting bracket)
1.4 kg; with Integral indicator (without mounting 
bracket)
EMC compliant standard: 
, 
EN61326, AS/NZS CISPR11
Material Cross Reference Table
SUS304 AISI 304
SUS316 AISI 316