Manual
    <6.  Maintenance>
6-5
IM 01C50B01-01E
Table 6.3  Problems, Causes and Countermeasures
Observed 
Problems
Possible Cause Countermeasure
Related Parameter
(BRAIN protocol) (HART protocol)
Output uctuates 
greatly.
Span is too narrow. Check the range, and 
change the settings to make 
the span larger.
F10:LRV
F20:URV
PV LRV (4)
PV URV (5)
Input adjustment by 
user was not corrctly 
done.
Clear the user adjustment 
(Sensor trim) value or set it 
to off.
J05:SNSR1 CLR
K05:SNSR2 CLR
Snsr1 Trim Act 
(123312)
Snsr2 Trim Act 
(123322)
Output adjustment by 
user was not correctly 
done.
Clear the user adjustment 
(output trim) value or set it 
to off.
L05:OUT CLR D/A Clr to Default 
(12343)
Transmitter 
outputs xed 
current.
The transmitter is in 
manual (test output) 
mode.
Release manual mode. 
(Make the transmitter return 
to Automatic Mode)
G10:OUTPUT MODE Loop test (122)
Input adjustment by 
user was not corrctly 
done.
Clear the user adjustment 
(Sensor trim) value or set it 
to off.
J05:SNSR1 CLR
K05:SNSR2 CLR
Snsr1 Trim Act 
(123312)
Snsr2 Trim Act 
(123322)
Output adjustment by 
user was not correctly 
done.
Clear the user adjustment 
(output trim) value or set it 
to off.
L05:OUT CLR D/A Clr to Default 
(12343)
Output is reversed.
(See note 1)
LRV is greater than 
URV.
Set the correct value to URV 
and LRV.
F10:LRV
F20:URV
PV LRV (4)
PV URV (5)
The transmitter is set to 
reversed output mode.
Set the transmitter to normal 
output mode.
H10:REVERSE OUT —
Parameters cannot 
be changed.
The transmitter is in 
write protect status.
Release write protect.
H40:WRITE PROTCT Chng wrt Protect
(Hot key)
Sensor backup 
function doesn’t 
work correctly.
Settings of Process 
Variables are not 
correct.
Set Sensor1 as PV and 
Sensor2 as SV.
B10:PV is
B20:SV is
PV is (11211)
SV is (11212)
Conguration of 
Sensor1 and Sensor2 is 
not correct.
• Ch
eck the type and wire 
settings for Sensor1 and 
Sensor2.
• Check the connection of 
Sensor1 and Sensor2.
D10:SENSOR1 TYPE
E10:SENSOR2 TYPE
Snsr1 cong (134)
Snsr2 cong (135)
Sensor Burnout is set 
to “off.”
Check the Sensor Burnout 
setting.
F40:BURN OUT Sensor barnout 
(14315)
Sensor backup mode is 
not enabled.
Change the Sensor Backup 
function to “enable.”
H20:SNSR BACKUP Snsr backup (14141)
Output damping 
doesn’t work.
Damping time constant 
is set to “0 second.”
Set correct value.
B12:PV DAMPING PV damp (1322)
Setting for “PV damping 
point” is too small.
If output uctuation is great, 
set a greater value for PV 
damping point than current 
setting. (Initial setting is “2%” 
of output)
B13:DMP POINT PV damp point 
(1323)
Note 1:  If the reversed output is desired and necessary setting was done by user, it is not considered as a problem.