    <5.  Wiring>
5-5
IM 01C50B01-01E
Adapter body
Rubber packing
Washer
Packing box
Grand
Clamp ring
Clamp nut
Union coupling
Union cover
O-ring
Lock nut
Lock nut
Cable
Be sure to apply 
non-hardening sealant to the 
threads for water proofing.
F0512.ai
CAUTION
Figure5.12 FlameproofGlandPackingAdapter
lnstallation
■ Flameproofmetalconduitwiring
•  A seal tting must be installed near the terminal 
box connection port for a sealed construction.
•  Ap
ply a nonhardening sealant to the threads of 
the terminal box connection port, exible metal 
conduit and seal tting for waterproong.
F0513.ai
Non-hazardous
area
Hazardous
area
Flameproof
heavy-gauge
steel conduit
Tee
Drain plug
Gas sealing
device
Flameproof flexible
metal conduit
Apply a nonhardening
sealant to the threads of
these fittings for
waterproofing
Seal fitting
After wiring, impregnate the fitting
with a compound to seal tubing.
Figure 5.13  Typical Wiring Using Flameproof Metal 
Conduit
5.6  Grounding
Grounding is always required for the proper 
operation of transmitters. Follow the domestic 
electrical requirements as regulated in each 
country. For a transmitter with built-in lightning 
protector, grounding should satisfy ground 
resistance of 10Ω or less.
Ground terminals are located on the inside and 
outside of the terminal box. Either of these terminals 
may be used.
WARNING
For TIIS flameproof type and intrinsically safe, 
grounding should satisfy Class D requirements 
(grounding resistance, 100Ω or less).
F0514.ai
Grounding
terminal
(Inside)
Grounding
terminal
(Outside)
Figure 5.14  Grounding Terminal