User Manual

<Appendix 1. List of Parameters for Each Block of the YTA>
A1-11
IM 01C50T02-01E
Relative
Index
Index Parameter Name
Default
(factory setting)
Write Description
80 2080 BACKUP_
RETURN_
SENSOR1
0 (DISABLE) O/S Setting 1 in this parameter switches the value
to be output from the sensor 2 input back to
the sensor 1 input:
0 = DISABLE
1 = ENABLE
81 2081 SENSOR_
BURNOUT_
DETECT
0 (on) O/S Switches on and off the sensor burnout
detection:
0 = On
1 = Off
In most cases, this parameter should be set to
0(ON). If this is set to OFF, the sensor burnout
detecting function will not correctly work.
82 2082 LIMSW_1_VALUE_
D
Indicates the value and status of limit switch 1.
83 2083 LIMSW_1_TARGET 0 O/S Value to be monitored by limit switch 1:
0 = PRIMARY_VALUE_1
1 = PRIMARY_VALUE_2
2 = SECONDARY_VALUE
3 = DIFFERENTIAL_VALUE
4 = AVERAGE_VALUE
5 = BACKUP_VALUE
84 2084 LIMSW_1
_SETPOINT
0 O/S Threshold of switching on limit switch 1
85 2085 LIMSW_1_ACT
_DIRECTION
0 (high-limit switch) O/S Type of limit switch 1:
0 = HI LIMIT (high-limit switch)
1 = LO LIMIT (low-limit switch)
86 2086 LIMSW_1
_HYSTERESIS
0 O/S Hysteresis of limit switch 1. Input of only a
positive number is valid.
87 2087 LIMSW_1_UNIT Unit of LIMSW_1_SETPOINT and LIMSW_1_
HYSTERESIS
88 2088 LIMSW_2_VALUE_
D
Indicates the value and status of limit switch 2.
89 2089 LIMSW_2_TARGET 0 O/S Value to be monitored by limit switch 2. The
setting and the corresponding value are the
same as those for limit switch 1 (LIMSW_1_
TARGET).
90 2090 LIMSW_2
_SETPOINT
0 O/S Threshold of switching on limit switch 2
91 2091 LIMSW_2_ACT_
DIRECTION
0 (high-limit switch) O/S Type of limit switch 2. The setting and the
corresponding type are the same as those for
limit switch 1 (LIMSW_1_ACT_DIRECTION).
92 2092 LIMSW_2
_HYSTERESIS
0 O/S Hysteresis of limit switch 2. Input of only a
positive number is valid.
93 2093 LIMSW_2_UNIT Unit of LIMSW_2_SETPOINT and LIMSW_2_
HYSTERESIS
94 2094 LIMSW_3_VALUE_
D
Indicates the value and status of limit switch 3.
95 2095 LIMSW_3_TARGET 0 O/S Value to be monitored by limit switch 3. The
setting and the corresponding value are the
same as those for limit switch 1 (LIMSW_1_
TARGET).
96 2096 LIMSW_3
_SETPOINT
0 O/S Threshold of switching on limit switch 3
97 2097 LIMSW_3_ACT
_DIRECTION
0 (high-limit switch) O/S Type of limit switch 3. The setting and the
corresponding type are the same as those for
limit switch 1 (LIMSW_1_ACT_DIRECTION).
98 2098 LIMSW_3
_HYSTERESIS
0 O/S Hysteresis of limit switch 3. Input of only a
positive number is valid.
99 2099 LIMSW_3_UNIT Unit of LIMSW_3_SETPOINT and LIMSW_3_
HYSTERESIS