<Appendix 1. List of Parameters for Each Block of the YTA>
A1-9
IM 01C50T02-01E
Relative
Index
Index Parameter Name
Default
(factory setting)
Write Description
36 2036 SENSOR_RANGE_
2
Range of sensor — Range of sensor 2.
37 2037 SENSOR_SN_2 — Auto Serial number of sensor 2.
38 2038 SENSOR_CAL_
METHOD_2
103 Auto Calibration method for sensor 2:
103 = Factory trim standard calibration
104 = User trim standard calibration
39 2039 SENSOR_CAL_
LOC _2
— Auto Shows and is used to record the location
where sensor 2 was calibrated.
40 2040 SENSOR_CAL
_DATE_2
— Auto Shows and is used to record the date when
sensor 2 was calibrated.
41 2041 SENSOR_CAL
_WHO_2
— Auto Shows and is used to record the person who
calibrated sensor 2.
42 2042 SENSOR _
CONNECTION_2
As specied by the
customer before
shipment
O/S Number of connection wires of sensor 2.
43 2043 SECONDARY
_VALUE
— — Indicates the terminal board temperature.
44 2044 SECONDARY
VALUE_UNIT
°C Auto Unit of the terminal board temperature.
45 2045 MODULE_SN Serial number — Serial number
46 2046 ALARM_SUM Enable — Shows the alarm summary for the transducer
block.
47 2047 PRIMARY_VALUE
_FTIME_1
2 second O/S Time constant (in seconds) of the rst-order
lag lter applied to the sensor 1 input . (0 to
99)
48 2048 CAL_STATE_1 0 (User Cal Off) O/S Indicates the validity of user calibration for
sensor 1:
0 =User Cal Off(Invalidate user-set
calibration values)
1 = User Cal On(Validate user-set calibration
values)
2 = Calibration Exec(User calibration mode)
49 2049 CJC_SELECT_1 0 (internal CJC) O/S Selects whether the terminal board
temperature or user-set constant
(CONSTANT_CJC_TEMP_1) is to be used
for cold junction compensation (CJC) for the
sensor 1 input. Valid for Thermocouple input
only.
0=Internal CJC
1=Constant CJC
50 2050 CONSTANT_CJC
_TEMP_1
— O/S User-set constant for CJC for the sensor 1
input. Setting 0 in this parameter disables
RJC. Valid only when CJC_SELECT_1 is set
to 1.
51 2051 WIRING _
RESISTANCE_1
0 O/S Wiring resistance of the sensor 1 input. For a
2-wire resistance input, the input resistance
minus this value is used as the temperature
value.
52 2052 SENSOR_MATCH
_R0_1
0 O/S Value of the factor R0 used in the sensor
matching function for the sensor 1 input
53 2053 SENSOR_MATCH
_A_1
0 O/S Value of the factor A used in the sensor
matching function for the sensor 1 input
54 2054 SENSOR_MATCH
_B_1
0 O/S Value of the factor B used in the sensor
matching function for the sensor 1 input
55 2055 SENSOR_MATCH
_C_1
0 O/S Value of the factor C used in the sensor
matching function for the sensor 1 input
56 2056 SENSOR_MATCH
_ALPHA_1
0 O/S Value of the factor α used in the sensor
matching function for the sensor 1 input
57 2057 SENSOR_MATCH
_DELTA_1
0 O/S Value of the factor δ used in the sensor
matching function for the sensor 1 input