User guide

3. OPERATION
IM 01C50T01-01E
3-17
1. Call up the “HART output” display. [1.Device
setup 4.Detailed setup 3.Output condition
2.HART output]
2. Select “4. Burst option”. Select a set of data to be
sent.
3. Return to “HART output” display and select “3.
Burst mode”. Select “On” to start the burst option.
Press SEND[F2] to send the setting. To release the
burst mode, select “Off” in this display.
If the transmitter is equipped with the integral indica-
tor, the LCD displays “B.M.”
3.5.10 Multi Drop
“Multi dropping” transmitters refers to the connection
of several transmitters to a single communication
transmission line. Up to 15 transmitters can be con-
nected when set in the multidrop mode. To activate
multi drop communication, the transmitter address
must be changed to a number from 1 to 15. This
change deactivates the 4 to 20 mA analog output,
sending it to 4mA . The alarm current is also disabled.
Setting of Multi drop
Call up the “HART output” display. [1.Device
setup 4.Detailed setup 3.Output condition
2.HART output]
Select “1. Poll addr” and set the polling address.(a
number from 1 to 15).
Press SEND[F2] to send the setting.
If the transmitter is equipped with the integral indica-
tor, the LCD displays “M.D.” and "F.O."
NOTE
1. When the identical address is set for two or
more transmitters in multidrop mode, commu-
nication with these transmitters is disabled.
2. Multi drop mode and Burst mode should not
be operated together at the same time.
Releasing the Multidrop mode
First, call up the “HART output” display. [1.Device
setup 4.Detailed setup 3.Output condition
2.HART output]
Select “1. Poll addr” and set the polling address to
“0”. Press SEND[F2].
3.5.11 Sensor Matching Function
This function is available only when optional specifica-
tion /CM1 is specified with YTA310 or YTA320.
Siginificant temperature measurement accuracy
improvement can be obtained using a temperature
sensor that is matched to a transmitter. This matching
process entails teaching the transmitter the relationship
between resistance and temperature for a specific RTD
sensor. This relationship, approximated by the
Callender-van Dusen equation, is described as follow-
ing :
Rt = R0 {1 + α (1+0.01δ ) t - αδ / 10
4
t
2
- αβ / 10
8
(t -100 ) t
3
}
where : Rt = Resistance (ohms) at
Tempearature t (
o
C)
R0 = Sensor -specific constant
(Resistance at t=0
o
C)
α (alpha) = Sensor-specific constant
δ (delta) = Sensor-specific constant
β (beta) = Sensor-specific constant
(0 at t>0
o
C)
Although the sensor curve is standardized, the exact
values for R0, α, δ and β are specific to each RTD
sensor and are obtained by testing each individual
sensor at various temperatures. These constants are
known as Callender-van Dusen constants.
Generally, the constants R0, A, B, and C are also used
as the characteristic coefficients of the RTD instead of
R0, α, δ and β. These are derived from IEC Standard
Curve and the relationship is described as followings ;
Rt = R0 {1 + At - Bt
2
+ C (t -100) t
3
}
where : Rt = Resistance (ohms) at
Tempearature t (
o
C)
R0 = Sensor-specific constant
(Resistance at t=0
o
C)
A = Sensor-specific constant
B = Sensor-specific constant
C =Sensor-specific constant
(0 at t > 0
o
C)
These two equations are equivalent. A model YTA
can cope with either case as above-mentioned.