Instruction Manual

<9. Parameter Summary>
9-6
IM 01C50E01-01EN
Object
ID
Attribute
ID
Label Description Default value Handling
5.
AI1 block
6.
AI2 block
*2
(continued)
103 Cal Point Lo Sets the zero-point adjustment for the input adjustment (zero-
gain adjustment ) of the sensor.
Be sure to perform adjustment with Cal Point Lo (zero-point)
rst.
--- W
104 Cal Point Hi Sets the gain-point adjustment for the input adjustment (zero-
gain adjustment) of the sensor.
--- W
105 Cal Point Clear Resets the input adjustment value of the sensor to the factory
setting.
0 W
106 Process Value
Type
Selects data to output to PV.Value.
0. % value after the scaling process is performed
1. Actual target value after the lter process is performed
0 W
107 Reference
Junction Unit
Sets the unit for Reference Junction Temp and External
Reference Junction Value.
Select any of °C (Celsius), K (Kelvin), °F (Fahrenheit), and °R
(Rankine).
°C W
108 Burn Out Type
*2
Sets the burnout of the PV value at the detection.
0: The direction specied by hard ware switch
1: Set to higher side
2: Set to lower side
0 W
(Note) R: Read only, W: Read and Write
(Note) “Factory NAMUR categoryrefers to the four categories (C: Check function, M: Maintenance required, F: Failure, and O: Off
specication) according to NAMUR NE107.
*1: NAMUR NE107 “Self-Monitoring and Diagnosis of Field Devices
*2: Applicable for dual input type with detachable antenna, Amplier housing code 8 and 9.
*3: Applicable for single input type with integral antenna, Amplier housing code 7.