Instruction Manual
<6. Operation>
6-3
IM 01C50E01-01EN
■ Provisioning work
This subsection describes provisioning work using
FieldMate as the provisioning device.
Provisioning work performs provisioning for each
eld wireless device using FieldMate and an
infrared adapter.
When using the Yokogawa recommended near
infrared adapter for the provisioning device, the
distance between the front glass of this instrument
and the infrared surface of the near infrared
adapter should be within 30 cm. For details on the
Yokogawa recommended infrared adapter, refer to
subsection 8.2 “Callibration Instruments Selection”.
Perform the following provisioning tasks.
• Setting provisioning information
• Creating a provisioning information le
1) Setting provisioning information
Set the device tag and Network ID using a
FieldMate provisioning function. The device
tag, Network ID, and join key are set in the eld
wireless device. It is not necessary to input
a join key because FieldMate automatically
generates it.
• Setting device tag
The device tag is used for the user to
recognize the eld wireless device.
• Setting Network ID
This is the Network ID for the eld wireless
network to which the eld wireless device is
connected. Set a value from 2 to 65535.
The eld wireless device is connected to the
eld wireless network corresponding to the
Network ID set by provisioning work.
2) Creating a provisioning information le
The following provisioned information is stored
in the provisioning information le.
• Network ID
• Device tag
• EUI64
• Join key
• Provisioner (name of the user who performed
provisioning work by FieldMate)
• Date (Time and date when provisioning was
performed by FieldMate)
This provisioning information le is required to
load from the eld wireless congurator to the
eld wireless integrated gateway. Store the le
carefully.
■ Connecting to a eld wireless network
The action after installing the battery pack varies
depending on the silence setting.
Mounting the battery pack automatically starts
a search for the eld wireless network and the
transmitter goes into the join state when the eld
wireless gateway is found. If the eld wireless
gateway is not found and a specied time based on
the silence mode has elapsed, a cycle of a 1-hour
pause and 6-minute search is repeated until the
transmitter can join the eld wireless network.
For details on the silence setting, refer to subsection
7.3.15 Switching to the Silence Mode.
F0603.ai
Mounting battery pack
Boot
Mounting battery pack
Pause (b)
Search failure for
the specified time
Infrared
communication
1 hour
passed
Search failure
for 6 minutes
Ready 2:
Searching (b)
(Connect)
(Connect)
Confirm connecting
status: Join (c)
(Publish)
Operation (d)
Deep sleep
setting
(Disconnect)
(Disconnect)
Ready 1:
Searching (b)
Deep sleep (a)
Infrared
communication
Figure 6.3 Wireless Status Transition