3.3 Setup Parameters
Example of Entering Measuring Range Parameters
When you enter the span upper and lower limit parameters of the SR command (the
input range setting command), you have to enter all the digits including those to the right
of the decimal point. For example, if you want to set the upper limit to 1.0000 V when the
measuring range is –2.0000 V to 2.0000 V, you have to enter “10000.” If you want to set
the limit to 0.5000 V, you have to enter “5000.”
The table below shows configuration examples.
Measuring
Range
Input Type
Parameter
Selectable Range of the
Measuring Range
Specified Range Parameter
VOLT 20mV –20.000mV
to
20.000mV –10.000mV
to
20.000mV –10000
to
20000
/SQRT 2V –2.0000V
to
2.0000V –2.0000V
to
0.5000V –20000
to
5000
TC R 0.0
to
1760.0 0.0
to
400.0 0
to
4000
K –200.0
to
1370.0 –200.0
to
1370.0 –2000
to
13700
RTD Pt100 –200.0
to
600.0 –10.0
to
500.0 –100
to
5000
DI LEVEL 0
to
1 0
to
1 0
to
1