Using the Ethernet Interface (/C7 Option)
1
2
3
4
5
6
App
Index
Setting the FX1000 Client (Modbus Client)
Assumes the settings other than that for the server and the command are left to default
values.
Registering the Destination Server
Register the FX1000 server to number 1.
The IP address of the FX1000 server is “190.168.1.101” as an example.
◊ Press MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to basic
setting mode), and select the Menu tab > Communication (Ethernet) > Modbus
client > Modbus server settings.
Item Settings
Port 502
Modbus server name 192.168.1.101
Unit Auto
Setting Command
◊ Press MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to basic
setting mode), and select the Menu tab > Communication (Ethernet) > Modbus
client > Command settings.
Item Settings
Command type R-M
First and Last C01
Server 1
Regi. 300001
Type INT16