User Manual

6-9
IM 04L21B01-17EN
Specifications
1
2
3
4
5
6
App
Index
Hold Register (shared with the Modbus slave function)
Common Items
The client device can read and write to the hold registers.
Communication input data is an option (/M1, /PM1, or /PWR1).
Reading from and Writing to Communication Input Channels
Communication input data can be handled on a computation channel by including the
data in the equation of a FX computation channel.
Hold Register Data Data Type
400001 Communication input data C01
16-bit signed integer
| |
400024 Communication input data C24
Precautions to be taken when the client device reads the data
The communication input data of the FX is floating point type, but the data is converted to
signed 16-bit integer when the data is read.
Precautions to be taken when the client device writes the data
Only data in signed 16-bit integer type can be written. Floating point values cannot be
written.
400601 Lower bytes of communication input data C01
32-bit floating point
400602 Higher bytes of communication input data C01
| |
400647 Lower bytes of communication input data C24
400648 Higher bytes of communication input data C24
Precautions to be taken when the client device writes the data
Input range: –9.9999E29 to –1E–30, 0, 1E–30 to 9.9999E29
If values outside this range are used on a computation channel, a computation error
occurs.
400301 Lower bytes of communication input data C01
32-bit signed integer
400302 Higher bytes of communication input data C01
| |
400347 Lower bytes of communication input data C24
400348 Higher bytes of communication input data C24
Note when a client device reads data
The FX communication input data is floating-point, but when it is read, it is converted to 32-
bit signed integer.
Note when a client device writes data
Data can only be written in 32-bit signed integer. Floating-point values cannot be written.
Operating Devices
You can use the following hold registers. You can perform a portion of the operations
by writing in the registers.
Internal switch
Lot number
Batch number
Recording (memory sampling) start and stop
Alarm ACK
Computation start, computation stop, computation reset, computation dropout ACK
Manual sampling, event data sampling start trigger, and snapshot
Message and free message writing
6.3 Modbus Protocol Specifications