Input Register (shared with the Modbus slave function)
Common Items
The client device can only read the input registers.
Decimal position and unit are not included. Specify them on the client device.
Details
Input Register Data Data Type
300001 Measured data of measurement channel 001
16-bit signed integer
| |
300012 Measured data of measurement channel 012
There is no decimal position information.
301001 Alarm status of measurement channel 001
Bit string
| |
301012 Alarm status of measurement channel 012
Register structure and alarm status values
2 1 4 3
4 bits 4 bits 4 bits 4 bits
4-bits
value Meaning
0 No alarm
1 High limit alarm
2 Low limit alarm
3 Difference high limit alarm
4 Difference low limit alarm
5 High limit on rate-of-change alarm
6 Low limit on rate-of-change alarm
7 Delay high limit alarm
8 Delay low limit alarm
Alarm level
Alarm status
302001 Lower bytes of the computed data of computation channel 101
32-bit signed integer
302002 Higher bytes of the computed data of computation channel 101
| |
302047 Lower bytes of the computed data of computation channel 124
302048 Higher bytes of the computed data of computation channel 124
Register structure
Example: Channel 101
Higher bytes Lower bytes
Register 302002
Computed data
Register 302001
There is no decimal position information.
303001 Alarm status of computation channel 101
Bit string
|
303024 Alarm status of computation channel 124
The register structure and alarm status values are the same as the alarm status of
measurement channels.
6.3 Modbus Protocol Specifications