User Manual

3-46
IM 04L21B01-17EN
QA Sets the number of mantissa
digits to display (/LG1 option)
Syntax
QAp1<terminator>
p1
Number of digits to display (2, 3)
Query
QA?
Example Set the number of mantissa digits to display to 2.
QA2
RH Sets LogType2 (/LG1 option)
Syntax
RHp1
p1
LogType2 (Linear, Pseudo)
Linear: Sets LogType2 to log linear input
Pseudo: Sets LogType2 to pseudo log input
Query
RH?
Example Set LogType2 to pseudo log.
RHPSEUDO
WF Sets the Modbus connection
limitation (/C7 option)
Syntax
WFp1<terminator>
p1
Modbus connection limitation (USE, NOT)
Query
WF?
Example Place limitations on Modbus connections.
WFUSE
WG Sets an IP address that is
allowed to connect through the
Modbus interface (/C7 option)
Syntax
WGp1,p2,p3<terminator>
p1
Registration number (1 to 10)
p2
Registration (ON, OFF)
p3
IP address (0.0.0.0 to 255.255.255.255)
Query
WG[p1]?
Example Allow connections from IP address
192.168.111.24. Use registration number 1.
WG1,ON,
192.168.111.24
Description You can use this command when Modbus
connection limitations have been placed (through
the use of the WF command).
WP Sets the phase, wiring system,
and input voltage (/PWR1 option)
Syntax
WPp1,p2<terminator>
p1
Phase and wiring system
Single-phase two-wire: 1P2W
Single-phase three-wire: 1P3W
Three-phase three-wire: 3P3W
p2
Input voltage (120V, 240V)
Query
WP?
Example Set the FX to use the single-phase two-wire
system with an input voltage of 120 V.
WP1P2W,120V
Description When parameter p1 is set to 3P3W, parameter
p2—the input voltage—is fixed to 240V.
If you change these settings, the VT ratio, CT ratio,
and integration low-cut settings will all be initialized.
XE Applies basic settings
Syntax
XEp1<terminator>
p1
Storage of settings (STORE, ABORT)
Example Save the basic settings.
XESTORE
Description To apply settings that you have changed using
the basic setting commands, you need to save
the settings using the XE command. Be sure to
save the settings using the XE command before
you change the execution mode from the basic
setting mode to the operation mode. Otherwise,
the new settings will not be applied.
YE Applies basic settings (cold
reset)
Syntax
YEp1<terminator>
p1
Application of settings
STORE
Saves the basic settings and
restarts the instrument
ABORT
Restarts the instrument without
saving the basic settings
Example Save the basic settings and restart the
instrument.
YESTORE
3.6 Basic Setting Commands