User Manual
3-34
IM 04L21B01-17EN
3.6 Basic Setting Commands
WU Sets the environment
Setups
GENERAL,BATCH,DISPLAY,MESSAGE,
INPUT,ALARM,SECURITY,MEDIA,MATH,
REPORT,SERVICEPORT,DECIMALPOINT,
POP3,
and
FTPSERVER
General environment settings
Syntax
WUp1,p2,p3<terminator>
p1
Setting type (GENERAL)
p2
Selects tag or channel number
TAG
Tag
CHANNEL
Channel number
p3
Language
ENGLISH
JAPANESE
CHINESE
GERMAN
FRENCH
ITALIAN
SPANISH
PORTUGUESE
RUSSIAN
KOREAN
Batch settings
Syntax
WUp1,p2,p3,p4<terminator>
p1
Setting type (BATCH)
p2
Batch function (OFF, ON)
OFF Disables the batch function
ON Enables the batch function
p3
Number of lot number digits (OFF, 4, 6, 8)
p4
Auto increment (ON, OFF)
Description Parameters p3 and p4 are valid when p2 is set to
ON.
Display settings
Syntax
WUp1,p2,p3,p4<terminator>
p1
Setting type (DISPLAY)
p2
Trend type
T-Y
T-Y display
p3
Partial expanded display (OFF, ON)
p4
Trend interval switching (OFF, ON)
Message settings
Syntax
WUp1,p2,p3,p4<terminator>
p1
Setting type (MESSAGE)
p2
Where to write messages that you enter
using keys
COMMON
All display groups
SEPARATE
The display group that you
specify
p3
Power failure message (OFF, ON)
p4
Change message (OFF, ON)
Input settings
Syntax
WUp1,p2<terminator>
p1
Setting type (INPUT)
p2
How to detect values that exceed the scale
FREE
When the measuring range is
exceeded
OVER
When ±105% of the scale is
exceeded
Description The setting of parameter p2 (how to detect
values that exceed the scale) is not applied to
channels that are set to Log scale (/LG1 option).
Alarm settings
Syntax
WUp1,p2<terminator>
p1
Setting type (ALARM)
p2
Alarm suppression function (OFF, ON)
Security settings
Syntax
WUp1,p2,p3<terminator>
p1
Setting type (SECURITY)
p2
Key
OFF
Disables the security features
KEYLOCK
Locks the keys
LOGIN
Enables the login function
p3
Communication
OFF
Disables the security features
LOGIN
Enables the login function
Description On models that do not have the Ethernet
interface (/C7 option), p3 is fixed to OFF.
Media settings
Syntax
WUp1,p2,p3<terminator>
p1
Setting type (MEDIA)
p2
Automatic saving (OFF, ON)
p3
Media FIFO (OFF, ON)
Example Use media FIFO.
WUMEDIA,ON,ON
Description • Parameter p3 is valid when p2 is set to ON.
• You cannot use this command on models that
do not have a CF card slot.
3.6 Basic Setting Commands