• Range > Type
Input type when Mode is Delta or Scale. See the description on Mode above.
• Range > Range
Input type details.
Setting Input Type Notes Setting Input Type Notes
20mV –20.000 mV to 20.000 mVDC Standard R Type R Standard
60mV –60.00 mV to 60.00 mVDC S Type S
200mV –200.00 mV to 200.00 mVDC B Type B
1V –1.0000 V to 1.0000 VDC K Type K
2V –2.0000 V to 2.0000 VDC E Type E
6V –6.000 V to 6.000 VDC J Type J
20V –20.000 V to 20.000 VDC T Type T
50V –50.00 V to 50.00 VDC N Type N
Pt Pt100 W Type W
JPt JPt100 L Type L
Level On/off (voltage) U Type U
Contact On/off (contact) WRe Type WRe
1-5V 0.800 V to 5.200 V
Setting Input Type Notes
Kp Kp vs Au7Fe /N3F
option
PLATI PLATINEL
PR PR40-20
NiMo NiNiMo
W/WRe W/WRe26
N2 Type N (AWG14)
XK XK GOST
Ni1 Ni100 (SAMA)
Ni2 Ni100 (DIN)
Ni3 Ni120
Pt100G Pt100 GOST
Cu100G Cu100 GOST
Cu50G Cu50 GOST
Pt200W Pt200 (WEED)
• Range > Span_L, Span_U
Input range. The selectable range is displayed on the screen.
Note
• You cannot set the same value to Span_L and Span_U.
• When the Mode is 1-5V or Sqrt, Span_L must be less than Span_U.
• Range > Scale_L, Scale_U
Input range after converting the unit.
The selectable range is from –30000 to 30000. The decimal place is determined by
the Scale_L setting. It can be set to the following positions: “X.XXXX,” “XX.XXX,” “XXX.
XX,” “XXXX.X,” or “XXXXX.”
Note
• The FX converts the measured value to a value within the range set by the Scale_L and
Scale_U values with their decimal points removed. For example, if the scale setting is
“–5 to 5,” the value is converted to a value within the span of “10”; if the scale setting is “–5.0
to 5.0,” the value is converted to a value within a span of “100.” In this case, the resolution
of the value converted to a span of “10” is lower than the value converted to a span of “100.”
To prevent the display from becoming rough, it is recommended that the scale be set so that
this value is greater than 100.
• You cannot set the same value to Scale_L and Scale_U.
• When the Mode is 1-5V or Sqrt, Scale_L must be less than Scale_U.
3.3 Setting the Input Range