Manual
14-5
IM 04L21B01-01EN
Setup Items
3
2
1
4
5
6
7
8
9
10
11
12
13
14
App
Index
Setup Item Selectable Range or Selections Default Value Setting
Mode = DI
Range Level/Cont Level
Span Lower Numerical value (0 or 1) 0
Span Upper Numerical value (0 or 1) 1
Mode = 1-5V
Range 1-5V 1-5V
Span Lower Numerical value (0.800 to 5.200) 1.000
Span Upper Numerical value (0.800 to 5.200) 5.000
Scale Lower Numerical value (–30000 to 30000; decimal place: 0 to 4) 0.00
Scale Upper Numerical value (–30000 to 30000) 200.00
Unit 6 characters or less −
Low-cut On/Off Off
Mode = Sqrt
Range 20mV/60mV/200mV/2V/6V/20V/50V/1V
Span Lower Numerical value (depends on the range) −
Span Upper Numerical value (depends on the range) −
Scale Lower Numerical value (–30000 to 30000; decimal place: 0 to 4) 0.00
Scale Upper Numerical value (–30000 to 30000) 200.00
Unit 6 characters or less −
Low-cut On/Off Off
Low-cut value Numerical value (0.0 to 5.0) 0.5
Mode = LogType1
Range 20mV/60mV/200mV/2V/6V/20V/50V/1V 2V
Span Lower Numerical value (depends on the range) –2.0000
Span Upper Numerical value (depends on the range) 2.0000
Scale Lower Mantissa (1.00 to 9.99) and exponent (–15 to 15) 2.00E0
Scale Upper Mantissa (1.00 to 9.99) and exponent (–15 to 15) 2.00E14
Unit 6 characters or less −
Mode = LogType2
Range 20mV/60mV/200mV/2V/6V/20V/50V/1V 2V
Span Lower Numerical value (depends on the range) –2.0000
Span Upper Numerical value (depends on the range) 2.0000
Scale Lower Mantissa (1.00 to 9.99) and exponent (–15 to 15) 2.00E0
Scale Upper Mantissa (automatically set to the same value as Scale Lower)
and exponent (–15 to 15)
−
Unit 6 characters or less −
Alarm
1, 2, 3, 4 On/Off Off
Type H: High/L: Low/h: delta H/l: delta L/ H
R: rate H/r: rate L/T: delay H/t: delay L
Value Numerical value
When Mode is LogType, this is set with the mantissa and the
exponent.
The range is 1.00E–16 to 1.00E+16 (the mantissa range is 1.00
to 9.99)
−
Relay On/Off Off
Number I01/I02/. . . /I06, I11/I12/. . . /I16 (depends on the options) I01
S01/S02/S03/. . . /S29/S30
Detect On/Off On
Meas channel > Tag, Memory, Delay
Setup Item Selectable Range or Selections Default Value Setting
First-CH, Last-CH Channel number 001
Tag > Characters 16 characters or less −
Memory sample > On/Off On/Off On
Alarm delay > Time Numerical value (1 to 3600; in seconds) 10
Meas channel > Moving average
Setup Item Selectable Range or Selections Default Value Setting
First-CH, Last-CH Channel number 001
On/Off On/Off Off
Count Numerical value (2 to 400) 2
14.1 Setting Mode Menu Map and Setup Items