Does the input meet
the specifications?
NO
NO
NO
NO
NO
YES
YES
YES
YES
Large measurement errors
Trend or digital wave value fluctuation
Trend going off the scale beyond either 0% or 100%
YES
Adjust the span and range
settings (section 3.3).
If you use input calibration
(/CC1 option), check the set values
for correction points (section 3.9).
Change the input wiring to meet
the specifications.
Is the input wiring correct?
Attach the input terminal cover
correctly.
Protect the input terminal from fans
and other sources of wind.
Keep the temperature fluctuation
near the input terminal to a
minimum.
Are the range/span
settings appropriate?
Are you taking
measures against noise?
Are
you keeping
the environmental temperature
constant (TC
input)?
Separate the input wiring from the
noise source.
Ground the recorder.
Ground the measured object.
Insulate the TC from the measured
object.
Use shielded cables for input.
Change the integration time
of the input A/D converter
(section 3.1).
Use the moving average of the
input (section 3.4).
Wire correctly
Install the terminal block correctly.
Fasten the terminal screws
correctly.
Insulate the RTD from the ground.
If burnt, replace the TC.
Is the input wiring parallel
with other equipment?
NO
NO
YES
YES
Is the RJC setting
correct (TC input)?
Stop the TC burnout upscale/
downscale function of other
equipment.
Ground the FX and other
equipment at one point.
Disconnect parallel wiring
(for example, use a
double-element TC)
Configure correctly.
Contact your nearest YOKOGAWA
dealer to have your FX serviced.
Section 3.2
Section 13.1
10.2 Troubleshooting